Descargar Imprimir esta página

CEMO 6/20 PROline Typ 90 Manual De Instrucciones página 29

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

It is also possible to use the cabinet without
mechanical exhaust air. However, it is important to
note the following:
The cabinet must be connected to earth to
prevent electrostatic charging (see section on
earthing).
There is a zone 1 explosive area inside the
cabinet.
There is a zone 2 explosive area within a radius
of 2.5 m around the cabinet and up to 0.5 m
above the floor. This area must be marked in
accordance with the Accident Prevention Regu-
lations (BGV A8):
In general, the national rules, laws and regula-
tions must also be observed here.
i
Important!
A mechanical ventilation system is man-
datory for the storage of highly flammable
liquids (H224).
In mechanically ventilated work rooms with
at least five air changes per hour, the zone 2
explosive area can be reduced to 1 m in front of
the safety cabinet and 0.5 m at the side of the
safety cabinet and to a height of 0.3 m above
the floor.
11. Grommets
Cable grommets can be installed in the cabinet
ceiling; see accessories for the order number. The
positions are marked on the cabinet as
Model
12/20 Type 90
6/20 Type 90
B
B
12. Earthing
The safety cabinet has a standard earth connec-
tion
on the ceiling.
C
C
Equipotential bonding must be installed by quali-
fied personnel. Check the conductivity after instal-
lation!
.
B
B
Number of grommets
2
1
B
B
C
C
GB
C
C
29

Publicidad

loading

Productos relacionados para CEMO 6/20 PROline Typ 90

Este manual también es adecuado para:

12/20 proline typ 90119111191611880