When installing or repairing the air conditioner and the
connecting line is not long enough, the entire connecting line
shall be replaced with the connecting line of the original
specification; extension is not allowed.
■
Use new connection pipe, unless re-flaring the pipe.
_
Requirements For lnstallation Position
• Avoid places of inflammable or explosive gas leakage or where
there are strongly aggressive gases.
• Avoid places subject to strong artificial electric/magnetic fields.
• Avoid places subJect to noise and resonance.
• Avoid severe natural conditions (e.g. heavy lampblack, strong
sandy wind, direct sunshine or h1gli temperature heat sources).
• Avoid places within the reach of cnildren.
• Shorten the connection between the indoor and outdoor units.
• Select where it is easy to perform service and repair and
where the ventilation good.
• The outdoor unit shalrnot be installed in any way that could
occupy an aisle, stairway, exit, tire escape, catwalk or any other
public area.
• The outdoor unit shall be installed as far as possible from the
doors and windows of the neighbors as well as the green plants.
■
Check nameRlate of outdoor unit to make sure whether the
refrigerant is R32.
■
Check the floor space of the room. The space shall not be less
than usable space(Sm
be installed at a well-ventilated place.
■
Check the surrounding environment of installation site: R32 shall
not be installed in the enclosed reserved space of a building.
■
When using electric drill to make holes in the wall, check first
whether there is pre-buried pipeline for water, electricity and gas.
lt is suggested to use the reserved hole in the roof of tfle walr
�---
_
Requirements of the mounting structure
• The mounting rack must meet the relevant national or industrial
standards in terms of strength with welding and connection
a reas rustproofed.
• The mounting rack and its load carry surface shall be able to
withstand 4 times or above the weight of the unit, or 200kg,
whichever is heavier.