MPL 111 S
2.4 T
ABLE OF TECHNICAL CHARACTERISTICS
GB
GENERAL FEATURES
MAX POWER (LTP)
CONTINUOUS POWER (PRP)
POWER FACTOR (Cos Φ)
THREEPHASE VOLTAGE
RATED FREQUENCY
GRADE OF PROTECTION
MAX TEMP. OF USE
MIN TEMP. OF USE
MAX ALTITUDE OF USE
COOLING AIR FLOW
DIMENSIONS
MASS
ENGINE
TYPE
MANUFACTER
MODEL
DISPLACEMENT
MAXIMUN POWER
n° OF CYLINDERS
RATED SPEED
SPEED CONTROL
INDUCTION SYSTEM
FUEL
INJECTION SYSTEM
FUEL FEEDING PUMPS
FUEL TANK CAPACITY
AUTONOMY AT 3/4 LOAD
COOLING
LUBRIFICATION SYSTEM
OIL SUMP CAPACITY
COMBUSTION AIR VOLUME
EXHAUST GAS MASS FLOW
ELECTRIC PLANT
STARTING
STARTING MOTOR
STARTING BATTERY
BATTERY CHARGER
STOPPING SYSTEM
ALTERNATOR
TYPE
ISOLATION CLASS
VOLTAGE REGULATOR
VOLTAGE STABILITY
FREQUENCY STABILITY
COOLING
POWER FACTOR (Cos Φ)
CONTINUOUS POWER A.C.
*
WITH TOW
Limited - time running power (LTP) ISO 8528-1
(1)
It is the maximum power that, under the environment conditions established by the norm ISO 3046/1, the generator group it is able to disburse for a maximum
of 500 hours for year, of which a maximum of 300 hours among the interval of maintenance prescribed by the builder. It is accepted the operation to
this power conditions the duration of the group.
An overload of the 10% is admitted only for regulation.
Prime power (PRP) ISO 8528-1
(2)
It is the available maximum power for a variable power cycle that the generator group is able to disburse for a boundless number of hours for year among
the interval of maintenance prescribed by the builder and under the environment conditions established by the norm ISO 3046/1. The middle power during
a period of 24 hours, doesn't have to exceed 80% of the PRP.
An overload of the 10% is admitted only for regulation.
GB
- 16
MODEL
1
2
L
W
H
MPL 111 S
111
106
0,8
400
50
IP 23
40
-15
1000
90
3050
1000
1450
1670
4 STROKE
DEUTZ
BF 4M 1013 EC
4764
97,3 / 71,5
4
1500
MECHANICAL
TURBO/INTERCOOLER
DIESEL
DIRECT
MECHANICAL
155
9
WATER
FORCED
8,5
5,76
8,63
12
ELECTRIC
12 - 3,1
12 - 100
14 - 55
STOP SOLENOID VALVE
SYNCHRONOUS, 4 POLES, SELF-REGULATED
H
ELECTRONIC
±2%
±5%
AIR
SINGLEPHASE 230V
1
L
1
N
L
L
2
3
kVA
kVA
V
Hz
°C
°C
m
3
m
/min
mm
mm
mm
kg
3
cm
CV - kW
rpm
L
h
L
3
m
/min
3
m
/min
V
V - kW
V - Ah
V - A