For group installation:
Model
DCA63S–4LP..
DCA63M–4LP..
DCA63L–4LP..
5.6.4
Motor Overload Protection
The devices are provided with load sensitive overload protection.
5.6.5
Surrounding Air Temperature Rating
The devices are suitable for an ambient temperature of 40 °C with nominal rating, and
max. 60 °C with derating. To determine max. output current rating at higher than 40 °C
up to 60°C, the current should be derated by 3 % per °C.
5.6.6
Wiring
Use copper wire (stranded wire) with a cross-section of at least AWG14 (or 2.5mm²)
for the power supply. Use an M12 supply cable or a suitable plug, M12 socket, L-co-
ded with UL approval.
5.6.7
Control Circuit
For control supply, use a secondary source with limited voltage: max. 42,4V DC. Con-
trol voltage input of the drive unit is rated to 24V DC.
Planificación de proyecto de la unidad de accionamiento
Frame Size
All listed class fuses
(currents are maxi-
mum, voltages mini-
mum values)
S
M
L
Manual del producto – MOVIMOT
Instalación conforme a UL
SCCR: 5 kA / 59 V
Inverse-Time Circuit
Breaker (currents are
maximum, voltages
minimum values)
110 A / 60 V DC
®
performance ELV
5
5
67