11.3 Display
11.3.1 LED display
Designation
Color
UL/UA
Green
Green
Red
Red
-
DIAG
Green
Red
Red
RUN
Green
Green
Green/red
-
ERR
Red
Red
-
L/A 1
Green
L/A 2
Yellow
-
11.4 Pin assignment
Table 14: Pin assignment X7E1/X7E2
Pin
Meaning
1
TD+
2
RD+
1
2
3
TD-
4
3
4
RD-
Housing
Ground
Table 15: Pin assignment power supply
Pin
Meaning
1
24 V DC power supply of the sensors/electronics (UL)
2
24 V DC actuator voltage (UA)
2
1
3
0 V DC power supply of the sensors/electronics (UL)
3
4
4
0 V DC actuator voltage (UA)
12 Disposal
Improper disposal will lead to pollution of the environment. Furthermore, the
materials can no longer be recycled.
Dispose of the product, the packaging and any escaping operating materials
u
in accordance with the applicable national regulations.
AVENTICS™ Modbus/TCP | 570092-BAL-AB | English
State
Meaning
Illuminates
Supply voltage is greater than 18 V .
Valve supply voltage is greater than
the lower tolerance limit
(21.6 V DC).
Flashes (1 Hz)
Supply voltage is greater than 10 V
and less than 18 V.
Flashes (1 Hz)
Supply voltage is greater than
26.4 V DC.
Illuminates
Valve supply voltage is less than
21.6 V DC v
Off
Supply voltage is less than 10 V DC.
Illuminates
State of the hardware is ok
Flashes (1 Hz)
Diagnostic message of the product
available
Illuminates
Hardware error of the valve system
Illuminates
Connected:
• OMB task is connected.
• At least 1 TCP connection is es-
tablished.
Flashes (1 Hz)
Ready:
• OMB task does not receive any
communication.
• Not configured
Flashes (5 Hz)
Waiting for communication:
• OMB task is configured.
Off
OMB task is not ready.
Illuminates
Communication error
Flashes (2 Hz),
System error
25 % brightness
Off
No error
Illuminates
Physical connection to network de-
tected.
Flashes
Receive data package.
Off
No physical connection to network
detected.
13 Troubleshooting
13.1 Procedure
Step 1: Check the system
In case of malfunctions, first check the system or the system part where the
u
product is installed. Check the following items:
• All connections. See g 9. Service.
• Settings. See
g 14. Technical
Step 2: Check the product
1. Make sure the system or system part is not under pressure or voltage.
2. Check the product based on the fault patterns described below.
3. Perform troubleshooting using the information under "Remedy".
If the malfunction cannot be eliminated as described under "Remedy": Disas-
semble the product and return it. See
4. After the malfunction has been eliminated; Put the system or product back
into operation.
13.2 Malfunction types
Error
Possible cause
No output pressure at the
• No power supply con-
valves
nected to the product.
See LED display
• No supply pressure avail-
able.
Output pressure too low
Supply pressure too low.
Power supply for the product
not sufficient.
Air is audibly escaping
Leakage between product
and supply.
Pneumatics incorrectly con-
nected.
Address assignment via DHCP
A save operation was trig-
server not possible
gered before the address
0x00 was set
Wrong address set.
LED UL/UA flashes green
The supply voltage is less
than the lower tolerance limit
(18 V DC) and more than
10 V DC
LED UL/UA illuminates red
The valve supply voltage is
less than 21.6 V DC
LED UL/UA is off
The supply voltage is less
than 10 V DC
LED UL/UA flashes red
The supply voltage is greater
than 26.4 V DC
LED DIAG flashes red
No module connected to the
product
Diagnostic message for open
load/short circuit at valve
available.
LED DIAG illuminates red
Diagnostic message available. Check module.
Internal connection error or
hardware error.
Product is not detected.
RUN LED flashes green
Not configured.
quickly
data.
g 4.3 Returning the
product.
Remedy
Apply power supply on plug
connector X1S.
Check power supply polarity.
Switch on system compo-
nent.
Connect supply pressure.
Increase supply pressure.
Check LED on the product.
Apply sufficient power sup-
ply.
Check the supply connection.
Check the pneumatic connec-
tion.
1. Separate power supply
2. Set the address between
1 and 254 (0x01and
0xFE).
3. Establish the power sup-
ply.
4. Wait 5 s, then separate
power supply.
5. Set address switch to
0x00.
6. Establish the power sup-
ply.
1. Separate power supply
2. Set the address. See
g 7.1.2 Assigning IP ad-
dress and subnet
Check power supply on plug
connector X1S.
Connect the module.
Check the connection of the
valves.
Contact manufacturer
Configure master for commu-
nication.
mask.
23