Controles Centrales: Luces, Persianas Y Temperatura - ABB i-bus KNX/EnOcean Manual Del Producto

Pasarela
Tabla de contenido

Publicidad

®

i-bus
KNX
FUNCIÓN
NAME
Status_ Daylight Harvesting
Status_ Dimming Level
Status_ Switching/Dimming Load
Status_ Illumination
Status_ Illumination Setpoint
Luz
Status_ Magnet Contact
Status_ Power Relay
Status_ Power Relay Timer
Status_ Repeater
Status_ Occupancy
Status_ Actual Setpoint
Status_ Alarm
Status_ Automatic/Override
Status_ Control Variable
Temperatura
Status_ Controller Mode On/Off
Status_ Controller Cool/Heat
Status_ Controller Mode
Status_ Fan Man/Auto
ABB STOTZ-KONTAKT GmbH
Eppelheimer Straße 82, 69123 Heidelberg, Germany
 +49 (0) 6221 701 607
 +49 (0) 6221 701 724
EG/A 32.2.1
DATAPOINT TYPE
LONGITU
D
DPT_NAME
1 bit
DPT_Enable
1 byte
DPT_Scaling
1 bit
DPT_Bool
2 bytes
DPT_Value_Lux
1 byte
DPT_Scaling
1 bit
DPT_OpenClose
1 bit
DPT_Switch
1 bit
DPT_Enable
1 bit
DPT_Enable
1 bit
DPT_Occupancy
2 bytes
DPT_Value_Temp
1 bit
DPT_Alarm
1 bit
DPT_Bool
1 byte
DPT_Scaling
1 bit
DPT_Switch
1 bit
DPT_Heat/Cool
1 byte
DPT_ErrorClass_HVAC
1 bit
DPT_Bool
FLAGS
DPT_ID R W T U
1.003
R
T
0 – Disable; 1 – Enable
5.001
R
T
%
1.002
R
T
0 – Switching; 1 - Dimming
9.004
R
T
lux
5.001
R
T
%
1.009
R
T
0 – Open; 1 – Close
1.001
R
T
0 – Off; 1 - On
1.003
R
T
0 – Disable; 1 – Enable
1.003
R
T
0 – Disable; 1 – Enable
1.018
R
T
0 – Not occupied; 1 – Occupied
9.001
R
T
ºC
1.005
R
T
0 – No alarm; 1 - Alarm
1.002
R
T
0 – Auto; 1 - Override
5.001
R
T
%
1.001
R
T
0 – Off; 1 – On
1.100
R
T
0 – Cooling; 1 – Heating
20.012
R
T
1 – Heat; 3 – Cool; 6 - Off
1.002
R
T
0 – Normal; 1 – Auto
www.abb.com/knx
Technische Helpline / Technical Support
 +49 (0) 6221 701 434 E-Mail: knx.helpline@de.abb.com
Manual de usuario r1.5 esp
VALORES
37 / 49

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Eg/a 32.2.1

Tabla de contenido