Pipe expanding method

NOTE:
Improper pipe expanding is the main cause of refrigerant leakage. Please expand the pipe
according to the following steps:
A: Cut the pipe
Confirm the pipe lenght accoding
to the distance of indoor unit and
outdoor unit.
Cut the required pipe with pipe cutter.
pipe
90º
leaning
B: Remove the burrs
Remove the burrs with shaper and
prevent the burrs from getting into
the pipe.
downwards
C: Put on suitable insulating pipe
D: Put on the union nut
Remove the union nut on the indoor
connection pipe and outdoor valve;
install the union nut on the pipe.
union pipe
pipe
pipe cutter
uneven
burr
pipe
shaper
E: Expand the port
Expand the port with expander.
NOTE
:
"A" is different according to the
diameter, please refer to the sheet
below:
Outer
diameter (mm)
ф6 - 6.35 (1/4")
ф9.52 (3/8")
ф12 - 12.7 (1/2")
ф15.8 - 16 (5/8")
F: Inspection
Check the quality of expanding port.
If there is any blemish, expand the
port again according to the steps
above.
smooth surface
the lenght is equal
49
hard
mold
expander
A(mm)
Max
1.3
1.6
1.8
2.4
improper expanding
leaning
damaged
crack
surface
pipe
Min
0.7
1.0
1.0
2.2
uneven
thickness
GB