Troubleshooting
THE OUTLET WATER
TEMPERATURE
EXCEEDS THE SET
VALUE
no
EXCESSIVE
WATER
FLOW, HIGH
THERMAL LOAD
yes
REDUCE THE FLOW
RATE OF THE WATER TO
BE COOLED
HIGH
AMBIENT
TEMPERATURE
yes
RETURN THE
AMBIENT
TEMPERATURE TO BELOW
THE
SPECIFIED LIMIT
FAULT
COMPRESSOR STOPS
DUE TO OPERATION
OF THE HIGH PRESSURE
SWITCH
PRESSURE SWITCH
BROKEN OR
WRONGLY
CALIBRATED
yes
REPLACE
PRESSURE SWITCH
no
CONDENSER
FINS
DIRTY
yes
CLEAN THE FINS
OF THE
CONDENSER
ICE007-010
REMEDY
CAUSE
COMPRESSOR SUC-
TION,
LIQUID LINE
FROSTED UP
REFRIGERANT
INSUFFICIENT
FILTER
WATER FLOW
CLOGGED
yes
yes
INCREASE THE
FLOW RATE OF THE
REPLACE
FLUID TO
THE FILTER
BE COOLED
no
CONDENSER SURFACES
CLOGGED
yes
CLEAR THE
FRONT
SURFACE
OF THE
CONDENSER
COMPRESSOR
RUNS FOR
LONG PERIODS,
NOISY
COMPRESSOR
COMPONENTS
DETERIORATED
yes
REPAIR OR
REPLACE
COMPRESSOR
no
LEAKS IN
REFRIGERANT
CIRCUIT,
FILTER
SYSTEM
CLOGGED
DISCHARGED
yes
yes
CHECK
FOR LEAKS,
REPLACE
ELIMINATE THEM,
THE FILTER
CHARGE
THE CIRCUIT