4.2. ADJuStMent SeleCtorS

n type units
n and A type protection unit keys
leD
Function
1
Alarm
2
Battery / Self-test
3
Ir
4
Isd/Ii
5
Ig/In
6
Communication
p and S type protection unit leDs
key
Function
a
M
b
c
d
e
f
26
ABW - Air Circuit Breaker
It indicates possibility of overload (it goes on in 90% of the adjusted
current and flashes above 105%)
Self-test of protection unit and battery charge
It indicates trip by overload
It indicates trip by short-circuit
It indicates trip by shortage current to ground
It indicates communication in network
Current measurement screen menu screen
Menu
Menu screen current measurement screen
TAP
Up cursor
It moves cursor one level up or increases value
Down
It moves cursor one level down or decreases value
cursor
Enter
It enters in secondary menu or defines value
Reset/ESC
It resets errors or exits current menu
A, p and S type units
Indication
Indication
Maintains current screen