40
ABW - Air Circuit Breaker
key
Upon pressing (2x) the key M from the measurement
M (2x)
screen, the screen of configuration of communication
in network (address) is accessed. The address can be
selected 1 thru 247.
Upon pressing the key Enter, the adjustment is saved,
or, upon pressing the key Esc/Reset, one returns to the
measurement screen without saving it. Once saved, the
word "SAVE" is shown on the screen.
Upon pressing (3x) the key M from the measurement
M (3x)
screen, the screen of configuration of communication in
network (Baud rate) is accessed. The Baud rate can be
selected between 38,400, 19,200 and 9,600.
Upon pressing the key Enter, the adjustment is saved,
or, upon pressing the key Esc/Reset, one returns to the
measurement screen without saving it.
Once saved, the word "SAVE" is shown on the screen.
Upon pressing (4x) the key M from the measurement
screen, the screen of checking of clock is accessed.
M (4x)
The clock is shown in the modality 24h, and the point
between hour and minute flashes every second.
Upon pressing (5x) the key M from the measurement
screen, the screen of checking of events recorded is
accessed. The last 10 events are recorded.
M (5x)
The information recorded is: current of shortage, type
of shortage, phase of occurrence, time and date of
shortage.
Example:
Ii: Type of shortage. 1,600 A: current of shortage. :
phase of shortage.
If there are no events recorded, the screen at the side will
be displayed.