Commissioning
Code
No.
Name
Operating Mode
V/f reference point
V
boost (optimization
min
of torque behavior)
C 7
Frequency threshold
(Q
)
min
C
Chopper frequency
1
Slip compensation
14
Possible Settings
Lenze Selection
2
0
Linear characteristic with
Auto-Boost
1
Square-law characteristic with
Auto-Boost
2
Linear characteristic with constant
V
boost
min
3
Square-law characteristic with
constant V
boost
min
4
Vector speed control
5
Vector torque control
6
Enhanced linear characteristic
with Auto-Boost
7
Enhanced linear characteristic with
constant V
boost
min
Note
• Settings 4...7 require Motor Calibration using c48
• Settings 4 and 5 require proper setting of C86...C91 prior to calibration
• Settings 6 and 7 require proper setting of C88...C90 prior to calibration
50.0
25.0
{Hz}
Set the rated motor frequency
(nameplate) for standard applications
0.0
{%}
C16 not active in Vector mode (see C14)
Set after commissioning: The unloaded
motor should run at slip frequency (approx.
5 Hz), increase C16 until motor current
(C54) = 0.8 x rated motor current
0.0
0.0
{Hz}
2
0
4 kHz
1
6 kHz
2
8 kHz
3
10 kHz
0.0
0.0
{%}
C21 not active in Vector mode (see C14)
ENGLISH
IMPORTANT
• Linear characteristic: for standard
applications
• Square-law characteristic: for fans and
pumps with square-law load characteristic
• Auto boost: load-dependent output voltage
for low-loss operation
• Vector speed control: for single-motor
applications requiring higher starting
torque and better speed regulation
• Vector torque control: for single-motor
applications requiring torque control
independent of speed
• Enhanced: for single or multiple
motor applications that require better
performance than settings 0...3, but
cannot operate in vector mode
999
40.0
240
See c17 and c18, selection 7
• As chopper frequency is increased, motor
noise is decreased
• Observe derating in Section 2.2
• Automatic derating to 4 kHz at 1.2 x Ir
40.0
Change C21 until the motor speed no longer
changes between no load and maximum
load
smd006