2
Technical data
2.1
Standards and application conditions
Conformity
Approvals
Max. permissible motor cable
length
(1)
Input voltage phase imbalance
Humidity
Output frequency
Environmental conditions
Temperature range
Installation height
Vibration resistance
Earth leakage current
Enclosure (EN 60529)
Protection measures against
Operation in public supply networks
(Limitation of harmonic currents
according to EN 61000-3-2)
(1) For compliance with EMC regulations, the permissible cable lengths may change.
(2) The additional measures described only ensure that the controllers meet the requirements of the EN 61000-3-2.
The machine/system manufacturer is responsible for the compliance with the regulations of the machine!
Technical Data
CE
Low Voltage Directive (2006/95/EC)
UL 508C
Underwriters Laboratories - Power Conversion Equipment
shielded:
50 m (low-capacitance)
unshielded:
100 m
< 2%
< 95% non-condensing
0...240 Hz
Class 3K3 to EN 50178
Transport
-25 ... +70 °C
Storage
-20 ... +70 °C
Operation
0 ... +55 °C (with 2.5 %/°C current derating above +40 °C)
0 ... 4000 m a.m.s.l. (with 5 %/1000 m current derating above 1000 m a.m.s.l.)
acceleration resistant up to 0.7 g
> 3.5 mA to PE
IP 20
short circuit, earth fault, overvoltage, motor stalling, motor overload
Total power
connected to
Compliance with the requirements
the mains
< 0.5 kW
With mains choke
0.5 ... 1 kW
With active filter (in preparation)
> 1 kW
Without additional measures
ENGLISH
(2)
5