Code
No.
Name
Current limit
Accel boost
Configuration -
analog input
C
Voltage - DC injection
brake (DCB)
Fixed setpoint 1
(JOG 1)
Fixed setpoint 2
(JOG 2)
Fixed setpoint 3
(JOG 3)
Frequency setpoint
Torque setpoint/range
C
Output frequency
Motor voltage
DC bus voltage
Motor current
Controller load
C
Motor torque
Heatsink temp
Possible Settings
Lenze Selection
200
30
{%}
Reference: Tmd rated output current
0.0
0.0
{%}
0
0
0...10 V
1
0...5 V
2
-10...+10 V
3
0...20 mA
4
4...20 mA
5
4...20 mA monitored
WARNING!
When running with -10...+10V reference (C34=2), a loss of reference will result in 5%
motor speed (0.05xC11).
Note
When C34 = 2:
• Rotation is determined by the polarity of the -10...+10 V signal:
+0.1...+10 V = CW and -0.1...-10 V = CCW (all other rotation commands are disabled)
• C11 sets maximum frequency in both directions (C10 is not active)
• CE1...CE4 = 6 or 7 will only start the controller, not select rotation
4.0
0.0
{%}
20.0
0.0
{Hz}
30.0
0.0
{Hz}
40.0
0.0
{Hz}
0.0
{Hz}
100
0
{%}
0.0
{Hz}
0
{V}
0
{V}
0.0
{A}
0
{%}
0
{%}
0
{C}
ENGLISH
Commissioning
200
• When the limit value is reached, either the
acceleration time increases or the output
frequency decreases
• When c73 = 0, max setting is 167%
20.0
Accel boost is only active during acceleration
• Voltage reference applied to 8U
• Tmd does not provide -10 V supply for
C34 = 2
• C34 = 2 disabled in vector torque mode
• Current reference applied to 8I
• C34 = 5 will trigger
below 2 mA
50.0
• See CE1...CE4 and c06
• Confirm motor suitability for use with DC
braking
240
Lenze setting: active at E1 = HIGH
240
Lenze setting: active at E2 = HIGH
240
Lenze setting: active at E1 = HIGH and E2
= HIGH
240
Display: Setpoint via analog input, function
UP/DOWN, or LECOM
400
• When C14 = 5 and C01 = 1, 5, 7, 9, 11,
sets the torque setpoint
• When C14 = 5 and C01 = 0, 2, 4, 6, 8, 10,
sets the torque range for C34
240
Display
999
Display
999
Display
400
Display
255
Display
400
Display: vector mode only (C14 = 4, 5)
255
Display
IMPORTANT
fault if signal falls
15