6. Calibration instructions
Then the pressure at which the contact is desired to break again must be applied.
Now the respective hysteresis potentiometer must be adjusted (
goes out again. The switching hysteresis is adjustable within a range of 0 ... 15 %.
1. Potentiometer for
switching hysteresis
2. Potentiometer for
switching points
WIKA Operating Instructions Differential Pressure Transmitter
CE
) until the LED
3. LCD (optional)
4. Signal
5. Power Supply
6. Product No.
7. Alarm contacts
(optional)
8. Span potentiometer
9. Zero potentiometer
10. Process connection
GB