Description Of Working - baltur TBG 55 Manual De Instrucciones

Ocultar thumbs Ver también para TBG 55:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

DESCRIPTION OF WORKING

TBG 55
Closing switch 1, if the thermostats are closed, the voltage
reaches the command and control equipment
(switches on LED 2) which start it working. The fan motor is
thus switched on (LED 3) to carry out the
preventilation of the combustion chamber.
The ignition transformer is then switched on (LED 4) and,
after 2 seconds, the gas valves .
In particular:
a) The main two-stage valve has a device to adjust gas
supply to the first (LED 5) and second flame (LED 6).
b) The safety valve is an ON/OFF type.
c) The combustion air can be manually regulated by means
of a gate (see page 41). Bearing in mind the burner is an
ON/OFF type, the position in which the air damper must be
regulated is that necessary for working at maximum desired
E
supply.
The presence of the flame is detected by the detection
N
device and allows the equipment to go on to the completion
of the ignition stage with the ignition transformer off. Sub-
G
sequently the second flame (LED 6, opening of the second
main stage valve).
L
If there is no flame, the equipment stops at "safety lock-out"
(LED 7) within 3 seconds from the first flame opening of the
I
main valve.
If there is a "safety lock-out", the valves immediately close
S
again.
To release the equipment from this safety position you have
to press button 8 on the display panel.
H
Equipment or
programmer
LME 22.331A2
LME 22.233A2
Safety
Preventilation
time
time
s
s
3
30
3
30
TBG 55P -210P
Closing switch 1, if the thermostats are closed, the voltage
reaches the command and control equipment (switching
on of LED 2) which starts it working. The fan motor is thus
switched on (LED 3) to carry out the preventilation of the
combustion chamber, at the same time the air damper
control servomotor moves to the opening position corre-
sponding to the second flame, thus the preventilation takes
place with the air damper in second flame position.
At the end of the preventilation stage the air damper goes
back to the first flame position and then the ignition tran-
sformer switches on (LED 4) and, after 2 seconds, the gas
valves (LED 5).
Note that:
a) The main two-stage valve has a device to adjust gas
supply to the first (LED 5) and to the second flame (LED 6).
b) The safety valve is an ON/OFF type.
c) The air damper is activated by an electric servomotor
(see adjustment page 69), remember that when the burner
stops because the thermostat is triggered, the damper is
moved by the servomotor back to its closed position.
The flame's presence is detected by control device and al-
lows the equipment to proceed to the ignition stage with the
switching off of the ignition transformer. Subsequently the
second flame switches on (increase of combustion air and
opening according to the main second stage valve LED 6)
If there is no flame, the equipment stops at "safety lock-out"
(LED 7) within 3 seconds from the first flame opening of the
main valve.
If there is a "safety lock-out", the valves immediately close
again.
To release the equipment from its safety position you have
to press button 8 on the display panel.
Post
Opening time
Pre-
-
ignition
ignition
1st flame valve
and the 2nd flame valve
s
s
2
2
2
2
10 / 18
0006081041_201102
time travel
opening
damper
s
s
11
12
11
30
time travel
closing
damper
s
12
30

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Tbg 55 pTbg 85 pTbg 120 pTbg 150 pTbg 210 p

Tabla de contenido