Emerson Vilter VSS Serie Manual De Instalación, Operación Y Mantenimiento página 186

Tabla de contenido

Publicidad

ICF 20
ICFS - stop valve module
ICFR - manual regulating valve module
ICFN - stop/check valve module
ICF 25 - 40
ICFS - stop valve module
ICFR - manual regulating valve module
ICFN - stop/check valve module
© Danfoss A/S (AC-MCI/MWA), 2012-12
Before remounting the cap on the modules
ICFS (stop valve module), ICFR (manual regulating
valve module) or ICFN (stop/check valve module)
please ensure that the gasket is present in the
cap. Then tighten the cap with 16 Nm (12 ft lbs).
Packing gland
If the packing gland is leaking, tighten it
carefully with a wrench.
Do not apply too much force.
Danfoss recommends that you conduct a
stepwise tightening of the packing gland.
For each turn check for possible leaks.
Before remounting the cap on the modules
ICFS (stop valve module), ICFR (manual regulating
valve module) or ICFN (stop/check valve module)
please ensure that the gasket is present in the
cap. Then tighten the cap with 24 Nm (18 ft lbs).
DKRCI.PI.FT0.C4.02 / 520H5450
ICFO - manual opening module
ICFE - solenoid valve module
3

Hide quick links:

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Vilter vsm serie

Tabla de contenido