The following modifications may be made during configuration:
If the expansion vessel is larger than 100 litres, set DS_A1 at OFF.
If you want the pumps to be exchanged every 24 hours and not at each restart, set DS_A2 at ON.
If you do not want protection against too rapid restarts, set DS_A3 at OFF.
If you do not want protection against lack of water, set DS_A4 at OFF.
If you want to bring the delay in switching off the pumps from 2 to 4 seconds, set DS A6 at OFF.
If you do not want to use the pump P1 set DS_A7 at ON.
If you do not want to use the pump P2 set DS_A8 at ON.
If you intend to use a set-point between 7 and 16 bar, set DS_B5 at ON.
If you intend to use pressure switches, set DS_B7 at OFF.
8.16 Regulating the rated current of the pumps (Imax), Set point (SP) and differential
restarting pressure (DP)
With a straight tip screwdriver, position the indices in the centre of the graduated scales, as shown in Figure 53, so
that:
Imax indicates the rated current of the installed pumps, which you can find on the pump data plate.
SP indicates the desired set point pressure.
DP is the pressure variation, in percentage of the set point, necessary to restart the pumps.
Attention, the differential restarting pressure is calculated as SP * DP. If the set point is 4 bar and DP is
50%, the pressure differential RP is 2 bar.
8.17 System operation
Pressure switches:
The operating logic is the following:
Pressure switch connected to input B starts and stops Pump 1.
Pressure switch connected to input C starts and stops Pump 2.
Pressure sensor:
RP is the pressure differential, and indicates the pressure variation around the Set Point for which the pumps are
switched on. In systems with a display it is set directly. In systems without a display, DP is set as a percentage of the
Set Point. RP = SP*DP. For further information see Figures 54 and 55.
The operating logic is the following:
The first pump starts when the pressure falls below the Set Point and it stops when it reaches the Set Point
pressure + RP.
The second pump starts when the pressure falls below the Set Point minus RP, or 2% of the Set Point if
vessels over 100 litres are used. It stops when the set point pressure + RP is reached in the system.
Figure 53: Regulating the rated current SP and DP
Pressure boosting operation with pressure switches
Pressure switch
P1
B = CLOSED
Pressure switch
P2
C = CLOSED
Table 11: Pressure boosting operation with pressure switches
ENGLISH
Start
105
Stop
Pressure switch
B = OPEN
Pressure switch
C = OPEN