GE AF-600 FP Guía Rápida página 5

Ocultar thumbs Ver también para AF-600 FP:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Installation
Voltage
200-240 V
380-480 V
3
3
525-600 V
525-690 V
Table 3.1 Minimum Airflow Clearance Requirements
3.3.2 Lifting
Check the weight of the unit to determine a safe
lifting method
Ensure that the lifting device is suitable for the
task
If necessary, plan for a hoist, crane, or forklift with
the appropriate rating to move the unit
For lifting, use hoist rings on the unit, when
provided
3.3.3 Mounting
Mount the unit vertically
The drive allows side by side installation.
Ensure that the strength of the mounting location
will support the unit weight
Mount the unit to a solid flat surface or to the
optional backplate to provide cooling airflow (see
Illustration 3.2 and Illustration 3.3).
Improper mounting can result in overheating and
reduced performance.
Use the slotted mounting holes on the unit for
wall mounting, when provided.
4
AF-600 FP Quick Guide
Power Size
Clearance a/b
0.25-3.7 kW 1/3-5 HP
100 mm/4 in
5.5-30 kW 7.5-40 HP
200 mm/8 in
>30 kW/40 HP
225 mm/10 in
0.37-7.5 kW 1/2-10 HP
100 mm/4 in
11-55 kW 15-75 HP
200 mm/8 in
>55 kW/75 HP
225 mm/10 in
0.37-7.5 kW 1/2-10 HP
100 mm/4 in
11-55 kW 15-75 HP
200 mm/8 in
>55 kW/75 HP
225 mm/10 in
all
225 mm/10 in
Illustration 3.2 Proper Mounting with Backplate
Item A is a backplate properly installed for required airflow
to cool the unit.
Illustration 3.3 Proper Mounting with Railings
NOTE
Backplate is needed when mounted on railings.
DET-759A

Publicidad

Tabla de contenido
loading

Tabla de contenido