4.3.5.3 Drawout Cassette Side Secondary
Disconnect
Use the following procedure to install the
Drawout Secondary Disconnect accessory.
Installation of Cassette side Secondary
disconnect:
1. Remove the screw shown in the Fig. 8.
2. Assemble the plate as shown in the Fig. 9.
3. Assemble the new SD block as shown in Fig.
10 & 11.
4. Complete the wiring of the new accessories
to the secondary disconnect block (refer wiring
diagram on the next page). Assemble back the
breaker in the cassette.
Note:
Secondary Disconnect Block B is required when:
1. Any "ZONE SELECTIVE INTERLOCKING"
options are selected in breaker/trip unit
Catalogue Digit 18
2. Any "ADVANCED FEATURES" are selected in
breaker/trip unit Catalogue Digit 19.
3. A COIL SIGNALLING CONTACT OPTION is
selected, Digit 12
4. A READY TO CLOSE signal via the trip unit is
selected, Digit 13
5. Any of the following OPTIONAL Aux. Contact
Switches are selected in Digit 12
- 8NO/NC POWER RATED
- 3NO/NC POWER RATED + 2NO/NC HIFI
- 4NO/NC POWER RATED + 4NO/NC HIFI
Note:
Side Secondary Disconnects are specifically
intended for 5-High ("high density") equipment
designs.
With Side Mounted Disconnects (SSD), the
following Aux Switches are not valid (In Digit 12):
– Auxiliary Switch, 8NO+8NC (Power Rated) or
– Aux. Switch, 4NO/4NC (Power Rated) +
4NO/4NC (High Fidelity)
Table 1.19: Terminal Wiring
Tables 1.19 Cablagem dos terminais
Number of Terminals
/ Numero de Terminais
Terminal capacity
/ Capacidade dos terminais
Screw type (bare conductors)
/ Tipo parafuso (condutores)
Ring/spade terminal system
/ Terminais de olhal/ponteira
4.3.5.2 Régua de bornes adicional no
Berço
Utilize o seguinte procedimento para instalar a
régua de bornes adicional no Berço.
Instalação da régua de bornes adicional no
Berço:
1. Retire os parafusos como se mostra na Fig.8
2. Monte a placa como se mostra na Fig. 9
3. Monte a nova régua adicional como se mostra
nas Fig. 10 e 11
4. Realize a cablagem dos novos acessórios na
régua de bornes (veja esquema de ligações na
pág. seguinte). Volte a introduzir o disjuntor no
berço.
Nota:
A régua de bornes B é necessária quando:
1. Se elege qualquer opção ZSI (Selectividade
condicionada) da unidade de disparo, Dígito de
catálogo 18
2. Se elege qualquer "OPÇÕES AVANÇADAS" da
unidade de disparo, Dígito de catálogo 19
3. Se elege um contacto de sinalização de
bobina, Dígito de catálogo 12
4. Se elege sinal de Preparado para fecho via
unidade de disparo, Dígito de catálogo 13
5. Se elege qualquer das seguintes opções de
contactos auxiliares, Dígito de catálogo 12
- Contactos standard 8NA/8NC
- Contactos standard 3NA/3NC + Contactos
baixo nível 2NA/2NC
- Contactos standard 4NA/4NC + Contactos
baixo nível 4NA/4NC
Nota:
A régua de bornes adicional está destinada
especificamente para desenho de
equipamentos 5 (Alta densidade).
Com a régua de bornes adicional (SSD), não se
podem utilizar os seguintes contactos auxiliares
(Dígito 12)
- Contactos standard 8NA/8NC o
- Contactos standard 4NA/4NC + Contactos
baixo nível 4NA/4NC
/
Cableado de bornas
/
Número de bornas
/
Capacidad de las bornas
/
Tipo de tornillo (conductores desnudos)
/
Sistema de terminales de punta u horquilla
ACCESSORIES
EntelliGuard G
4.3.5.2 Regletero de bornas adicional en
la Cuna
Utilice el siguiente procedimiento para instalar el
regletero de bornas adicional en la Cuna.
Instalación del regletero de bornas adicional
en la Cuna:
1. Retire los tornillos como se muestra en la Fig.8
2. Monte la placa como se muestra en la Fig. 9
3. Monte el nuevo regletero adicional como se
muestra en las Fig. 10 y 11
4. Realice el conexionado de los nuevos
accesorios en el regletero de bornas (vea
esquema de conexionado en la pág. siguiente).
Vuelva a introducir el interruptor en la cuna.
Nota:
El regletero de bornas B es necesario cuando:
1. Se elige cualquier opción ZSI (Selectividad
condicionada) de la unidad de protección, Dígito
de catálogo 18
2. Se elige cualquier "OPCIONES AVANZADAS" de
la unidad de protección, Dígito de catálogo 19
3. Se elige un contacto de señalización de
bobina, Dígito de catálogo 12
4. Se elige señal de Preparado para cierre vía
unidad de protección, Dígito de catálogo 13
5. Se elige cualquiera de las siguientes opciones
de Contactos auxiliares, Dígito de catálogo 12
- Contactos estándar 8NA/8NC
- Contactos estándar 3NA/3NC +
Contactos bajo nivel 2NA/2NC
- Contactos estándar 4NA/4NC +
Contactos bajo nivel 4NA/4NC
Nota:
El regletero de bornas adicional está destinados
específicamente para diseño de equipos 5 (Alta
densidad).
Con el regletero de bornas adicional (SSD), no se
pueden utilizar los siguientes contactos
auxiliares (Dígito 12)
- Contactos estándar 8NA/8NC o
- Contactos estándar 4NA/4NC +
Contactos bajo nivel 4NA/4NC
78
1x
0,35 - 2,5 mm²; 22-12 AWG
2x
0.35 - 2.5 mm²; 22-14 AWG
1x
0,5 - 2,5 mm²; 20-12 AWG
4
.3
4.3-13