Descargar Imprimir esta página

Beko QWIK-PURE 100 Instrucciones De Montaje Y De Uso página 18

Publicidad

Utilisation • Operação
Maintenance • Mantenimiento
Entretien • Manutenção
OEKOSORB cartridge
OEKOSORB cartucho
OEKOSORB catouche
OEKOSORB cartucho
18
Operation • Servicio
Weight
Peso
Poids
Peso
19.8 lbs
Order Ref.
Nº de referencia
No de commande
N° de referência
4004442
english
To ensure trouble-free operation, ob-
serve all the points listed under Main-
tenance:
The constituents of the compressor
condensate will depend on the specific
application.
It is part of the operator's duty of care to
take the necessary precautions, where
appropriate.
english
Note:
• It is recommended that an original
OEKOSORB cartridge be kept in stock
at all times.
• Only use OEKOSORB cartridge to en-
sure operational reliability. The original
cartridges are identified by their label-
ling (C) and the test seal.
• Do not use any other material. Oth-
erwise the correct functioning of the
QWIK-PURE (wastewater quality,
through-put capacity, service life) can-
not be guaranteed.
• Remove plastic bag before cartridge
installation!
Procedure
1. Keep the plastic bag of the new car-
tridge for wrapping up the old one.
2. Shut off condensate inlet
3. Open QWIK-PURE lid.
4. Lift cartridge and allow it to drain. Put
filter into the plastic bag and close bag
tightly.
5. Clean cartridge area.
6. Insert the new cartridge slowly and
ensure that the guide pins (A) fit into
the container holes (B).
7. Put back the lid.
8. Open condensate inlet.
9. Ensure correct disposal of the
fouled cartridge in the plastic bag
provided.
Note:
Insure new cartridge is completely
saturated with clean water prior to
putting back into operation.