Specifications; Generator; Transfer Switch - Briggs & Stratton 190839GS Manual Del Propietário

Ocultar thumbs Ver también para 190839GS:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Briggs & Stratton Power Products Home Generator
System
Owners
Manual
_ois byEo,o_'_ Cu_ _am_e"
A switch on the control panel is labeled "Set Exercise"
(depicted on page I O).The specific day and the specific time
of day this switch is pressed is programmed into the
control board memory.This date and time is then used to
automatically initiate the system exercise cycle.
To perform
the Set Exercise procedure:
I.
Choose the day and time you want your Home
Generator System to exercise.
2.
On that day and time, set the AUTO/OFF/MANUAL
switch to OFF.
3.
Press and hold down the "Set Exercise" switch.The
Diagnostic LED blinks.
4.
Hold the switch down until the Diagnostic LED stops
blinking. Release the Set Exercise switch.
5.
Set the AUTO/OFF/MANUAL
switch to AUTO.
"Set
Exercise" is complete.
For example, if you press the "Set Exercise" switch on
Sunday morning at 10:00 AM, the unit will run an exercise
cycle the following Sunday at IO:00AM.
NOTE: "Set Exercise" will only work if the unit is in the
Automatic
mode and this exact procedure is followed.The
exerciser does not need to be re-set if the 15Amp fuse is
removed or changed.The exerciser will need to be re-set if
the 12 Volt DC battery is disconnected.
If you want to change the day and time the unit exercises,
simply perform the "Set Exercise" procedure at the exact
weekday and time you want it to take place.
SPECIFICATIONS
Generator
Model ....................
01679-0
Rated Maximum Power (LP*)...
10.0 kW
Rated Maximum Load Current:
at 240 Volts ...............
41.7 Amps
at 120Volts ...............
83.3 Amps
Rated AC Voltage ............
120/240 Volts
Rated Frequency ............
60 Hz at 3600 rpm
Phase.....................
Single Phase
Power Factor ...............
1.0
NG Fuel Supply Pressure .....
5-14 in W.C. (127-356 ram)
LP Fuel Supply Pressure ......
I 1-14 in V_C. (279-
356 mm)
Normal Operating Range ....
-20°F (-28.8°C) to 104°F
(40°C)
Output Sound Level ........
70 dB(A) at 23 f_. (7 m) at
full load
Shipping Weight ............
482 Ibs.
* Natural gas rating will depend on specific fuel but typical
derates are between 10 to 20% offthe LPgas rating.
Transfer
Switch
Maximum Circuits ...........
10
Maximum Load/Circuit:
from Generator ...........
41.7 Arnps
from Load Center ..........
50Amps
Maximum Watts .............
I0,000
W
15