Assembly And Installation - EdilKamin ECOIDRO Guía De Instalación, Uso Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

ASSEMBLY AND INSTALLATION

(the Dealer)
safety distance from flammable materials
floor protection sheet
Refer to the local regulations in the country of use for anything not
expressly shown. In Italy, refer to Italian standard 10683/2005 or later
modifications, and Italian law No. 46/90, along with any regional or
local health authority regulations.
If the stove is to be installed in a block of flats, consult the block
administration before installing.
COMPATIBILITY CHECK WITH OTHER DEVICES
According to Italian standard UNI 10683/2005, the stove must NOT
be installed in the same room as extractor fans, type A and B gas
equipment, or devices which lower the pressure in the room.
ELECTRICAL CONNECTION CHECK:
(PUT THE PLUG IN AN ACCESSIBLE PLACE)
The stove is fitted with an electrical power cord for connection to a
230 V 50 Hz socket, preferably protected with a thermal-magnetic
circuit breaker. Voltage variations of greater than 10% may impair
stove operation (if not already installed, fit a suitable residual current
circuit breaker). The electrical system must comply with the law; in
particular make sure the earth circuit is in working order. The power
supply line must have a suitable cross-section for the equipment rating.
LOCATION
For correct operation the stove must be level.
Check the load-bearing capacity of the floor.
FIRE SAFETY DISTANCES
The stove must be installed in compliance with the following safety conditions:
- minimum safety distance at the sides and back from medium-level flammable materials: 40 cm.
- easily flammable materials must not be located less than 80 cm from the front of the stove.
- if the stove is installed on a flammable floor, a sheet of heat insulating material must be placed between the stove and the floor,
which protrudes by at least 20 cm at the sides and 40 cm at the front.
Objects made of flammable materials must not be placed on the stove or at less than the safety distance from it.
If the smoke outlet pipe is connected to walls made of wood or other flammable materials, it must be insulated with ceramic
fibre or other materials with similar characteristics.
AIR INTAKE
The room where the stove is located must have an air intake with cross section of at least 80 cm2 to ensure replenishment of the
air consumed by combustion.
SMOKE OUTLET
The stove must have its own smoke outlet (it must not discharge into flues shared with other devices).
The smoke leaves the stove through the 8 cm diameter pipe at the back. A T-section with condensation trap and bleeder must be
fitted at the beginning of the vertical section. The stove smoke outlet must be connected with the outside using black painted or
steel pipes (resistant to 450°C), without obstructions.
The pipe seals must be air-tight. To seal and insulate (if necessary) the pipes, material that withstands up to 300°C must be used
(silicone or high temperature mastic).
The only horizontal section allowed may be up to 2 m long. The horizontal sections must have a minimum upward gradient of
3%. Up to two 90° bends may be included.
If the smoke outlet does not end in a flue, a vertical section with wind guard at the end is essential.
The vertical duct section may be indoor or outdoor. If the smoke duct is outdoor, it must be insulated.
If the smoke duct ends in a flue, the flue must be authorized for solid fuel. If it is more than 150 mm in diameter, it must be rene-
wed by inserting an internal pipe and sealing the smoke outlet from the brickwork. All sections of the smoke duct must be
inspectable. If it is fixed, cleaning inspection openings must be provided.
Recommended installations are shown in the following figures.
27

Publicidad

Tabla de contenido
loading

Tabla de contenido