REFRIGERATION SPECIFICATIONS

SINGLE CIRCUIT

models
REFRIGERANT CHARGE
COOLING ONLY
HEAT pUmp
ADDITIONAL CHARGE
Connecting pipes 1/2" liquid pipe
Connecting pipes 5/8" liquid pipe

DUAL CIRCUITS

models
REFRIGERANT CHARGE
COOLING ONLY
HEAT pUmp
ADDITIONAL CHARGE
Connecting pipes 1/2" liquid pipe
Connecting pipes 5/8" liquid pipe
NOTE:
The 125, 155 and 185 units are supplied pre-filled with their refrigerant charge.
The 205, 255, 305, 405m, 405, 505, 605, 755 and 905 units are supplied filled with a nitrogen charge. The
installer must fill the system with the stated volume of refrigerant at the time of installation.
The charges are stated for 4m pipe lengths. For longer pipe lengths, the refrigerant charge must be adjusted in
accordance with the details provided.
Refrigerant fluid charge values are given for information purposes only. The actual charge required must be
adjusted during installation in order to optimise performance.
The products' installation and environment represent vital parameters for their proper operation.
125 - 125V 155 - 155V
g
3030
4730
5530
g
3200
4830
5950
g/m
48
50
g/m
/
/
405
505
g
2 x 5410
2 x 7060
2 x 9930
g
2 x 5160
2 x 7110
2 x 9430
g/m
125
125
g/m
210
210
7
185
205
255
5910
6060
5910
6010
/
125
125
55
/
210
605
755
905
2 x 10160
2 x 12300
2 x 10160
2 x 12300
125
125
125
210
210
210
305
405m
8760
11550
8700
11550
125
125
210
210