This operation should be performed expertly by qualified
professionals (refrigeration engineer) (brazing, vacuum,
charge, etc ...).
Unroll the pipes carefully, in the opposite direction to the
spirals, to avoid bending them.
REFRIGERATION PIPE BENDING
The bending radius of the pipes should be equal to or more than 3,5 times de outside
diameter of the pipe.
Do not bend the pipes consecutively more than three times and do not make more than
12 bends over the complete length of the link.
TIGHTENING TORQUE FOR REFRIGERANT VALVES
LIQUID:
(small valve) 15Nm
1 Newton-meter = 0,1 meter-kilo
FOLLOW THE CONNECTION INSTRUCTIONS FOR THE VALVES WITH NON-REMOVABLE
MEMBRANES
Line up the 2 half couplings.
Remove the protective plugs on each coupling.
Check if the valves are greased on the inside; if not, lubricate them slightly with oil fit refrigeration
use.
Give a few clockwise turns by hand, to make sure threading is engaged properly.
Continue screwing clockwise with a wrench, while holding the rear part ( tube side ) with another
wrench placed counter-clockwise, until it is firmly tighten . Just then, resume locking with an additional
1/4 turn of the wrench.
The reason for this last step is to crimp the internal metal gasket.
NOTE
Prior to final butt-screwing, a slight freon leak may be noticed which should stop quickly.
Proceed to leak tests.
THESE COUPLINGS WHILE CIRCUIT IS UNDER REFRIGERANT PRESSURE
SUCTION:
(large valve) 55Nm
FOR SAFETY'S SAKE NEVER DISCONNECT
13