Technical Data; General; Power Supply - Eaton xChargeIn Manual De Instalación

Ocultar thumbs Ver también para xChargeIn:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 249

Technical data

12
Technical data
12.1

General

Overvoltage category:
Protection class:
Protection type:
Protection against mechanical impact:
Rated short-time withstand current:
Internal residual direct current detection
Residual Direct Current Detecting Device
(RDC-DD):
12.2

Power supply

Power consumption
Rated supply voltage (Europe)
Power consumption
Rated current (configurable):
Line frequency:
Mains forms:
Supply terminals
Type:
Cable feed:
52
A Series:
X Series / S Series / M Series:
A Series:
X Series / S Series:
M Series:
III according to EN 60664
I
IP54
IK08 (except for cylinder lock)
< 10 kA effective value according to EN
61439-1
≥ 6 mA
230 V
3 x 230 V / 400 V
Idle: 2 W
Plugged: 3 W
Charging: 5.5 W
Idle: 3 W
Plugged: 4.5 W
Charging: 6.5 W
Idle: 4 W
Plugged: 5 W
Charging: 7 W
10 A / 13 A / 16 A / 20 A / 25 A / 32 A
1-phase or 3-phase
50 Hz
TT / TN / IT
Spring-type terminal
Top (surface), rear (flush)
Installation manual V1.01
xChargeIn
© EATON

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido