Technical Data; General; Power Supply - Eaton xChargeIn Serie Manual De Instalación

Estación de carga para vehículos eléctricos
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 320

Technical data

12
Technical data
12.1

General

Charge mode:
Overvoltage category:
Protection class:
Protection class:
Protection against mechanical impact:
Rated short-time withstand current:
Residual direct current detecting device
(RDC-DD):
Ventilation during charging:
12.2

Power supply

Power consumption A Series
Rated supply voltage (Europe):
Internal consumption:
Rated current (configurable):
Line frequency:
Mains forms:
Power supply X Series / S Series
Rated supply voltage (Europe):
Internal consumption:
Rated current (configurable):
Line frequency:
Mains forms:
Power supply M Series
Rated supply voltage (Europe):
Internal consumption:
Rated current (configurable):
Line frequency:
Mains forms:
308
Mode 3 in accordance with IEC 61851-1
AC charging
III in accordance with EN 60664
I
IP54
IK08 (except for cylinder lock)
< 10 kA (effective value in accordance with
EN 61439-1)
> 6 mA (characteristic in accordance with
IEC 62955, < 10 s)
Not supported
230 V
Idling: 2 W, plugged in: 3 W, charging: 5.5 W
10 A / 13 A / 16 A / 20 A / 25 A / 32 A
1-phase
50 Hz
TT / TN / IT
3 x 230 V / 400 V
Idling: 3 W, plugged in: 4.5 W, charging:
6.5 W
10 A / 13 A / 16 A / 20 A / 25 A / 32 A
1-phase or 3-phase
50 Hz
TT / TN / IT
3 x 230 V / 400 V
Idling: 4 W, plugged in: 5 W, charging: 7 W
10 A / 13 A / 16 A / 20 A / 25 A / 32 A
1-phase or 3-phase
50 Hz
TT / TN / IT
Installation manual V1.05
xChargeIn
© EATON

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido