In accord with the current circulating through the conductors (maximum 16 mm
for a solid nucleus cable, 35 mm
Furthermore, for sizing the wire, keep in mind the range of admitted diameters by the M25 packing glands
supplied by Ingeteam installed in the unit. This range is from 7 ~ 17 mm.
9.2.2. INGECON SUN 3Play TL (28~40 kW)
Versions P and P+
Each string has two protection fuses (one at each pole) and current monitoring.
The maximum admissible currents per string are the following:
28TL M
11 A
Below we indicate the admitted section limits in the connections. The minimum sections indicated may not be
enough relative to the type of installation, so the installer must size the wiring relative to its needs.
The unit is delivered with 15 Adc 1000 V fuses.
Versions S and S+
The maximum admissible currents are the following, relative to the type of connection and inverter model:
118
DC input sections in TL M units
Terminal connections in S and S+ versions
15TL M
for a flexible nucleus cable or 50 mm
2
rigid cable nucleus)
Maximum DC current input in TL units
Quick connections in P and P+ versions
28TL
11 A
Maximum DC current input in TL M units
Quick connections in P and P+ versions
DC input sections in TL units
Quick connections in P and P+ versions
28TL
1.5 ~ 10 mm
DC input sections in TL M units
Quick connections in P and P+ versions
28TL M
1.5 ~ 10 mm
Maximum DC current input in TL units
Terminal connections in S and S+ versions
28TL
52 A
20TL M
33TL
11 A
33TL M
11 A
33TL
2
33TL M
40TL M480
2
33TL
61 A
ABO2011IQM01_A - Installation and Operation Manual
DC connection
24TL M480
2
for a semi-
2
40TL M480
11 A