Display control
The available configuration codes are:
Code
0
3
5
6
Once this configuration is made, the string current measurement is activated and configured.

10.7. Configure the power limit

This option limits, as a percentage of the nominal, the maximum active power that the inverter can inject into the
grid.
To configure the power limit access Main Menu > Settings > Power settings and indicate the percentage of
maximum active power desired.

10.8. Configuring the country/ regulation

Relative to the applicable regulation at the installation, these inverters must work according to a series of
parameters.
To configure the inverter according to the regulation, access Main Menu > Advanced settings > Country regulations.
Select the country where the inverter will be installed. If the country is not on the list, select Worldwide and select
the applicable regulation. After selecting the regulation, configure the voltage and frequency.

10.9. Configuring the Modbus ID

The Modbus ID is the inverter's identification number within the communications bus. These inverters have two
RS-485 communication lines, so you can configure the Modbus number for two different buses.
To configure it or the Modbus numbers access Main Menu > Settings > Modbus ID.
The COMM 1 ID is the inverter´s ID within the communication bus generated from the RS-485 communication
integrated by default into the unit.
The COMM 2 ID is the inverter´s ID within the communication bus generated from the optional communication
accessory installed in the INGECON Connect. If the inverter has self-consumption mode activated like Self-limited
CG EM24 the modification of the COMM 2 ID has no repercussions.

10.10. Configuring the auxiliary relay

These inverters have a potential-free output which can have several functions:
Closing the relay in the event of an insulation fault (default option).
Closing the relay in the event of a grid, voltage or frequency out of range alarm.
Closing the relay in the event of any alarm in the inverter.
Closing the relay upon connection of the inverter to the grid.
Closing the relay if the estimated power of the PV array exceeds the load power. When this mode is
selected, the user will also have to enter another configuration parameter: the load power.
To configure the auxiliary relay access the Main menu > Settings > Close auxiliary relay.
ABO2011IQM01_A - Installation and Operation Manual
Configuration codes
Inverter
Versions S and S+ (measurement of string currents not available)
INGECON SUN 3Play 10TL
INGECON SUN 3Play 15TL
INGECON SUN 3Play 20TL
INGECON SUN 3Play 10TL M
INGECON SUN 3Play 15TL M
INGECON SUN 3Play 20TL M
INGECON SUN 3Play 24TL M480
INGECON SUN 3Play 28TL
INGECON SUN 3Play 33TL
INGECON SUN 3Play 28TL M
INGECON SUN 3Play 33TL M
INGECON SUN 3Play 40TL M480
Ingeteam
DE
EN
ES
FR
IT
PT
129

Hide quick links:

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido