Cabling Length; Photovoltaic Panels; External Dc Switch - Ingeteam INGECON SUN 10TL Manual De Instalacion Y Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 147
Ingeteam

5.6. Cabling length

The inverter measures the voltage in its connection terminals. For this reason, the installer must use an AC cable
with a sufficiently low impedance so that increasing the voltage in the cable (between the distribution transformers
and the unit) does not cause the unit to be disconnected due to high voltage.

5.7. Photovoltaic panels

The stray capacity of the PV array must be lower than:

5.8. External DC switch

In units that do not incorporate a DC switch by default (version S) must install an external switch.
104
INGECON SUN 3Play
10TL
15TL
20TL
28TL
33TL
10TL M
15TL M
20TL M
24TL M480
28TL M
33TL M
40TL M480
PV array stray capacity
< 3.4 μF
< 3.4 μF
< 3.4 μF
< 3.4 μF
< 3.4 μF
< 3.4 μF
< 3.4 μF
< 3.4 μF
< 2.8 μF
< 3.4 μF
< 3.4 μF
< 2.8 μF
ABO2011IQM01_A - Installation and Operation Manual
Preparation for installing the unit

Hide quick links:

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido