9. DC connection

This chapter explains the requirements and process for wiring the DC wiring to the unit.
Read carefully before starting the connection process.
INFO
Consult section "Important safety instructions" and the following instructions before working on the unit.

9.1. Safety instructions for the DC connection

DANGER
Make sure there is no voltage present on the unit before starting the connection.
Do not switch on the power to the unit until you have successfully made the rest of the connections and the unit is
closed.
Use the Personal Protective Equipment specified in the section "Personal Protective Equipment (PPE)".
While connecting the inverter, make sure of the proper installation of the cables on the unit´s terminals so that
parts of accessible wires do not remain live.
CAUTION
Ingeteam accepts no liability for any damages caused by incorrect connection.
INFO
The wiring must be routed inside the unit via a conduit, which is inserted through a coupling in order to
maintain the unit's protection class.

9.2. Wiring requirements for the DC connection

CAUTION
The cabling for the DC connection, besides complying with the sections indicated in this section, must comply
with the current standards of the country where the PV installation is located.
For all versions, use copper wire.
9.2.1. INGECON SUN 3Play TL (10~24 kW)
Versions P and P+
For inverters with P and P+ finishes there are two types of DC input connections: with quick connectors or
terminals via packing glands (supplied by Ingeteam).
If using quick connectors, each string has two protection fuses (one at each pole) and current monitoring.
If the connection is made via a terminal and packing glands, the protection fuses and current monitoring are not
operative.
The maximum admissible currents are the following, relative to the type of connection and inverter model:
Quick connections in P and P+ versions
10TL
11 A
116
Maximum DC current input in TL units
15TL
20TL
11 A
11 A
Terminal connections in P and P+ versions
10TL
15TL
37 A
37 A
ABO2011IQM01_A - Installation and Operation Manual
DC connection
20TL
37 A