If required, the system can be controlled in SERVICE MAN mode by switching all Dip Switched to ON
WARNING! This adjustment affects the safety level of the automatic system.
Check that the force applied to the road barrier beam complies with regulations in force.
Any change in speed requires a new calibration of the amperometric sensor.
A Faston (VMOT) connector is provided on the power supply transformer. This allows for the adjustment of
the road barrier motor speed at three different levels (18-23-26).
By positioning the Faston (VMOT) to 18 a lesser speed is provided, by moving the Faston to 26 a higher
speed is provided.
Should the VE.AM mobile stand or the VE.RAST rack be present, reduce the beam speed.
The control unit is provided with a series of self-diagnostic LEDs which permit to check all functions:
POWER LED
STOP LED
PHOT LED
OPN LED
CLS LED
PP LED
SWC LED
SWO-R LED
SWC-R LED
10
To adjust the road barrier speed
It flashes to indicate the presence of mains power supply
It switches off when the STOP button is activated
It switches off when the photocells are not aligned or in the presence of obstacles
It switches on when the OPEN button is activated
It switches on when the CLOSE button is activated
It switches on when the PP button is activated
It switches off when the SWC closing limit switch is activated
It switches off when the SWO-R opening braking limit switch is activated
It switches off when the SWC-R closing braking limit switch is activated
Diagnostics of LEDs