Output personalization
Function
Output voltage
Frequency
converter
(1)
Output frequency
Transfer to the
bypass AC input
Overload level
(1)
(1) These parameters may be modified only when the UPS is OFF.
ON/OFF personalization
Function
Start on battery
power
Automatic restart
Energy savings
Detection of phase/
neutral inversion
(SWF)

Battery personalization

Function
Battery test
Low-battery warning 20%
Selection of the
backup time
Battery protection
against excessive
discharges
86-86700-00EN A02 - Page 22
Factory Setting
120 Volts AC
(1)
Disabled
Automatic selection
(1)
Bypass AC power
must be within toler-
(1)
ances
100%
Factory Setting
Enabled
Enabled
Disabled
Enabled
Factory Setting
Weekly test
Automatic detection
of number of battery
modules
Enabled
Other available
Comments
settings
100 to 127 Volts AC
The connected devices are never trans-
Enabled
ferred to the bypass.
User selectable only if the frequency-
50 or 60 Hz
converter function is enabled.
Bypass AC power
may be outside
tolerances
30 / 50 / 70%
Alarm if threshold is overrun.
Other available
Comments
settings
Disabled
The UPS restarts automatically when AC
Disabled
power returns.
When function enabled, battery shuts
Enabled
down when power drops to <5%.
Neutral inversion (SWF) When function
Disabled
enabled, the UPS remains OFF if the
system detects phase/neutral inversion.
Other available
Comments
settings
No test / daily test /
monthly test
0 to 100%
Adjustable in 1% steps.
13 to 200 Ah
Excessive discharges when function
Disabled
disabled, EATON warranty no longer
applies.