2.4 — Specifications
2.4.1 — Generator
Output
Rated Voltage
Rated Maximum Load
Current (Amps) at 240
Volts (LP)*
Main Circuit Breaker
Phase
Rated AC Frequency
Battery Requirement
Weight (unit only in lbs./
kg)
Enclosure
Normal Operating
This unit is tested in accordance to UL 2200 standards with an operating temperature of -20 ºF (-29 ºC) to 122 ºF (50 ºC). For areas
Range
where temperatures fall below 32 ºF (0 ºC) a cold weather kit is required. When operated above 77 ºF (25 ºC) there may be a decrease
These generators are rated in accordance with UL 2200, Safety Standard for Stationary Engine Generator Assemblies, and CSA-C22.2 No. 100-04
Standard for Motors and Generators.
* Natural Gas ratings will depend on specific fuel Btu/joules content. Typical derates are between 10-20% off the LP gas rating.
** Circuits to be moved must be protected by same size breaker. For example, a 15 Amp circuit in the main panel must be a 15 Amp circuit in the transfer switch.
2.4.2 — Engine
Type of Engine
Number of Cylinders
Displacement
Cylinder Block
Recommended Spark Plug
Spark Plug Gap
Starter
Oil Capacity Including Filter
Recommended Air Filter
Engine power is subject to and limited by such factors as fuel Btu/joules content, ambient temperature and altitude. Engine power decreases about
3.5 percent for each 1,000 feet (304.8 meters) above sea level, and also will decrease about 1 percent for each 10 ºF (6 ºC) above 60 ºF (15 ºC)
ambient temperature.
The specification sheet for your generator was included in the documentation provided with the unit at the time of purchase. For additional
copies, consult your local Authorized Service Dealer for your specific generator model.
2.4.3 — Fuel Requirements
The engine has been fitted with a dual fuel carburetion system. The unit will run on natural gas or LP gas (vapor), but it has been factory set to
run on natural gas. The fuel system will be configured for the available fuel source during installation.
Recommended fuels should have a btu content of at least 1,000 Btus per cubic foot (37.26 megajoules per cubic meter) for natural gas, or at
least 2,500 Btus per cubic foot (93.15 megajoules per cubic meter) for LP gas (vapor).
NOTE: If converting to LP gas from natural gas, a minimum LP tank size of 250 gallons (946 liters) is recommended. See the Installation
Manual for complete procedures and details.
Automatic Standby Generator Owner's Manual
7 kW
240
29.2
30 Amp
1
60 Hz
Group U1, 12 Volts and 300 CCA Minimum (Generac Part No. OD4575)
280/127.3
Galvanneal Steel
in engine power. Please reference the engine specifications section.
GA-420
420 cc
Aluminum w/Cast Iron Sleeve
F7TC/ Champion N9YC
0.76 mm (0.030 in)
12 VDC
Approx. 1.2 Qt/1.1 L
Generac Part No. 0E9371A
1
7