3A SWITCHING OFF
Temporary switching off
In case of absence for short periods of time, set the mode selector
(3 - fig. 1a) to
(OFF).
In this way (leaving the electricity and fuel supplies enabled), the
boiler is protected by the following systems:
- Anti-frost device: when the temperature of the water in the boiler
falls below 5°C, the circulator and, if necessary, the burner are
activated at minimum output levels to bring the water tempera-
ture back to the values for safety (35°C). During the anti-frost
cycle, the symbol
appears on the digital monitor.
- Circulator anti-blocking function: an operation cycle is activated
every 24 hours.
- DHW Antifreeze (only when connected to an external storage
tank with probe): the function is activated if the temperature
measured by the storage tank probe drops below 5° C. A heat re-
quest is generated in this phase with the ignition of the burner at
minimum power, which is maintained until the water temperature
reaches 55° C. During the anti-frost cycle, the symbol
on the digital monitor.
Long period switching off
In case of absence for long periods of time, set the mode selector
(3 - fig. 1a) to
(OFF).
Then, close the gas tap present on the system. In this case, anti-
frost device is deactivated: empty the systems, in case of risk of
frost.
4A CONTROLS
At the beginning of the heating season, and occasionally during
use, make sure the hydrometer-thermohydrometer indicates cold
system pressure values between 0.6 and 1.5 bar: this avoids sys-
tem noise levels due to the presence of air. In case of insufficient
water circulation, the boiler will switch off. Under no circumstances,
water pressure must be below 0.5 bar (red field).
If this condition is checked, it is necessary to restore water pres-
sure in the boiler proceeding as follows:
- set the mode selector (3 fig.1a) to
- turn on the filling tap (L fig. 12) until the pressure value is be-
tween 1 and 1.5 bar.
Carefully close the tap. Replace the mode selector on the initial
position. If pressure drop is frequent, contact the Technical Assis-
tance Service.
5A LIGHT SIGNALS AND FAULTS (fig. 6a)
The operating status of the boiler is shown on the digital display,
below is a list of the types of displays.
To restore operation (deactivate alarms):
Faults A 01-02-03
Position the function selector to
set it to the required position
mode). If the reset attempts do not reactivate the boiler, contact the
Technical Assistance Centre.
Fault A 04
In addition to the fault code, the digital display shows the symbol
.
Check the pressure value indicated by the water gauge:
if it is less than 0.3 bar, position the function selector to
and adjust the filling tap (L fig. 12) until the pressure reaches a
value between 1 and 1.5 bar.
Then position the mode selector to the desired position
mer) or
(winter).
If pressure drops are frequent, request the intervention of the Tech-
nical Assistance Service.
Fault A 06
The boiler operates normally but cannot reliably maintain a con-
stant domestic hot water temperature, which remains set at around
50°C. Contact the Technical Assistance Centre.
Fault A 07
Contact the Technical Assistance Centre.
appears
(OFF)
(OFF), wait 5-6 seconds then
(summer mode) or
(winter
(OFF)
(sum-
BOILER STATUS
Stand-by
OFF status
ACF module lockout alarm
ACF electrical fault alarm
Limit thermostat alarm
Fumes thermostat
H2O pressure switch alarm
NTC domestic water fault
NTC heating fault
Parasite flame
Electric calibration min and max heating
Transient awaiting ignition
Fumes thermostat intervention
H2O pressure switch intervention
Preheating Function active
Preheating heat request
External probe present
Domestic water heat request
Heating heat request
Anti-freeze heat request
Flame present