4.3 Switching off
Temporary switching off
In case of absence for short periods of time, set the mode selector
(2 - fig. 1a) to
(OFF).
In this way (leaving the electricity and fuel supplies enabled), the
boiler is protected by the following systems:
- Anti-frost device: when the temperature of the water in the
boiler falls below 5°C, the circulator and, if necessary, the
burner are activated at minimum output levels to bring the water
temperature back to the values for safety (35°C). During the anti-
frost cycle, the symbol
- Circulator anti-blocking function: an operation cycle is
activated every 24 hours.
Long period switching off
In case of absence for long periods of time, set the mode selector
(2 - fig. 1a) to
(OFF).
Then, close the gas tap present on the system. In this case, anti-frost
device is deactivated: empty the systems, in case of risk of frost.
4.4 Light signals and faults (fig. 5a)
The operating status of the boiler is shown on the digital display,
below is a list of the types of displays.
To restore operation (deactivate alarms):
BOILER STATUS
Stand-by
OFF status
ACF module lockout alarm
ACF electrical fault alarm
Limit thermostat alarm
Fumes thermostat
H
O pressure switch alarm
2
NTC domestic water fault
NTC heating fault
Parasite flame
Electric calibration min and max heating
Transient awaiting ignition
Fumes thermostat intervention
H
O pressure switch intervention
2
External probe present
Domestic water heat request
Heating heat request
Anti-freeze heat request
Flame present
Faults A 01-02-03
Position the function selector to
set it to the required position
mode). If the reset attempts do not reactivate the boiler, contact the
Technical Assistance Centre.
Fault A04
In addition to the fault code, the digital display shows the symbol
Check the pressure value indicated by the water gauge:
if it is less than 0.3 bar, position the function selector to
and adjust the filling tap (L - fig. 12) until the pressure reaches a
value between 1 and 1.5 bar.
Then position the mode selector to the desired position
(summer) or
(winter).
If pressure drops are frequent, request the intervention of the
Technical Assistance Service.
Fault A06
The boiler operates normally but cannot reliably maintain a
constant domestic hot water temperature, which remains set at
around 50°C. Contact the Technical Assistance Centre.
Fault A07
Contact the Technical Assistance Centre.
appears on the digital monitor.
DISPLAY
-
OFF
A01
A01
A02
A03
A04
A06
A07
A11
ADJ
88°C
flashing
flashing
flashing
60°C
80°C
(OFF), wait 5-6 seconds then
(summer mode) or
4.5 Adjustments
The boiler has already been adjusted by the manufacturer.
If it is necessary to adjust it again, for example after extraordinary
maintenance, after replacement of gas valve or after gas
conversion, carry out the following procedure.
The maximum output adjustment must be carried out in the
sequence indicated exclusively by qualified personnel.
- Remove the shell unscrewing the fixing screws A (fig. 6)
- Unscrew by two turns the screw of the pressure test point
downstream the gas valve and connecting the pressure gauge
4.5.1 Maximum power and minimum domestic hot water
adjustment
- Fully open the hot water tap
- On the control panel:
- set the mode selector to
- turn the domestic hot water temperature selector to its
maximum (fig. 7a)
- Power the boiler setting the system main switch to "on"
- Check that the pressure on the pressure gauge is stable; or with
a milliammeter in series to the modulator, make sure that the
modulator supplies the maximum available current (120 mA for
G20 and 165 mA for LPG).
- Carefully prise out the protection cap of the adjustment screws,
using a screwdriver (fig. 14)
- With a fork spanner CH10 use the adjustment nut of the maximum
output in order to obtain the value indicated in table "Technical
data"
- Disconnect the modulator faston
- Wait until the pressure on the pressure gauge is stable at
minimum value
- Paying attention not to press the internal shaft, use an Allen
spanner to turn the red adjustment screw for domestic hot water
minimum temperature regulation, calibrating it until the pressure
gauge reads the value indicated in the table "Technical data"
- Reconnect the modulator faston
- Close the domestic hot water tap
- Carefully refit the protection cap of the adjustment screws.
4.5.2 Minimum and maximum heating electric adjustment
The "electric adjustment" function is activated and deactivated
exclusively by the jumper (JP1) (fig. 15).
ADJ
appears on the display to indicate that the calibration
procedure is underway.
The function can be enabled in the following way:
- by powering the card with the jumper JP1 inserted and the mode
selector in winter position, independently from the possible
presence of other operation request.
- by inserting the jumper JP1, with the mode selector in winter
position, without heat request in progress.
By activating the function the burner is ignited through
simulation of heat request in heating.
To perform calibration operations, proceed as follow:
- switch off the boiler
(winter
- remove the shell and access the card
- insert the jumper JP1 (fig. 15) to enable the knobs placed on the
control panel to the minimum and maximum heating adjustment
functions.
.
- make sure that the mode selector is in winter position (see
section 4.2)
(OFF)
- power the boiler.
Electric card in voltage (230 Volt).
- turn the heating water temperature adjustment knob B (fig. 16)
until it reaches the minimum heating value as indicated in the
multigas table
- insert the jumper JP2 (fig. 15)
- turn the domestic hot water temperature adjustment knob C (fig.
16) until it reaches the maximum heating value as indicated in
the multigas table
- remove the jumper JP2 to store the maximum heating value
- remove the jumper JP1 to store the heating minimum value and
to get out the calibration procedure
CIAO C.A.I. e
(summer) (fig. 2a)
7