Configuration Menu - Galletti EVO Manual De Instalacion Y Uso

Mando electrónico para terminales hidrónicos
Ocultar thumbs Ver también para EVO:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 99
The UP/DOWN arrows are used to scroll through the 24
time slots of every day of the week; scrolling is displayed
graphically by the scroll cursor at the bottom of the screen,
or in text, when the when the time slot is updated, at the top.
If you wish to edit the attribute (OFF, T1, T2, T3) of a slot
press SET to enter edit mode, change the attribute using the
UP/DOWN ARROW and press SET again to confirm.
Press PRG to move on to the next day of the week.
To duplicate a profile press the UP ARROW and MODE keys
at the same time; the day you wish to copy the profile to will
be copied will be highlighted: to change it use the UP/DOWN
ARROW keys and confirm with the SET key.
PARAMETERS MENU AND LISTS
To access the MENU press the PRG key. Use the UP/DOWN
ARROW keys to scroll through the various MENU items,
which are in the following order:
CONFIGURATION MENU (access using password 10):
see dedicated paragraph
ADJUSTMENT MENU (access using password 77): see
dedicated paragraph
CLOCK SETUP MENU (no password required): to set
date, time and day of week
TIME SLOTS MENU (no password required)
NETWORK AND CONNECTION MENU (access using
password 20)
OUTPUT DISPLAY MENU: to view the status of the
physical outputs (digital and 0-10V) on the board
OUTPUT TEST MENU (access using password 30):
forcing the physical outputs (digital and 0-10V) on the
board
INFO MENU: to view information on the installed
software.
EN
7
Controller for units
OPERATION MANUAL
IT IS strictly forbidden to reproduce this manual, even partially

CONFIGURATION MENU

LIST OF PARAMETERS
DESCRIPTION
DEFAULT
Unit type
Standard
Number of pipes
2 Pipes
Air probe
Display
Temperature display Celsius
Type of ventilation
Step
Valve configuration
Not included
Switching
From keyboard/
Summer/Winter
serial
DOUT Configuration
No use
Digital output logic
N.A.
Heater included
No
Water probe
No
installed
Number of water
1
probes 4-pipe unit
Humidity probe
No
installed
Turning Economy
No
on from digital input
Turning ON/OFF on
No
from digital input
Language
Italian
Stand-by Mode
Off
CONFIGURATION LIMITS
Unit configuration must take the following requirements into
account:
if there is a heater you will also need a water probe to
be installed:
if there is a heater and a valve, then the valve must be a
3-WAY (NO 2-WAY VALVES);
if Summer/Winter switching is set on "Auto on water
temp." then there must also be a water probe;
no heater must be installed on 4-pipe units;
with 4-pipe units with a single water probe, summer/
EVO
POSSIBLE VALUES
Standard - 2x1(4
speeds)
2 Pipes - 4 Pipes
Display - Board
Celsius - Fahrenheit
Step - Modulating
Not included - On/Off -
Modulating
From keyboard/serial
From Digital input
Auto on water temp.
Auto on air temp.
(see dedicated
paragraph)
N.A. – N.C.
No/Yes
No/Yes
1/2
No/Yes
No/Yes
No/Yes
Italian/English
Off - Clock -
Temperature
FC66003554
Rev 00

Publicidad

Tabla de contenido
loading

Tabla de contenido