DAS SETUP-MENÜ
BESCHREIBUNG
Minimum cooling SET limit
Maximum cooling SET limit
Minimum heating SET limit
Maximum heating SET limit
Minimum humidity SET limit
Maximum humidity SET limit
Humidity hysteresis
Offset on humidity reading
Minimum value of modulating ventilation
Maximum value of modulating ventilation
Air probe offset
Water probe offset
Heating water probe offset
Economy Hysteresis
Cooling water consent SET
Cooling water consent hysteresis
Heating water consent SET
Heating water consent hysteresis
Dehumidification water consent SET
Dehumidification water consent hysteresis
Valve water consent SET
Valve water consent hysteresis
Heater water consent SET
Heater water consent hysteresis
Temperature minimum control SET
Temperature minimum control hysteresis
Neutral zone
Default values RESET
DE
9
Steuerung für Endgeräte
DEFAULT
10.0 °C
35.0 °C
5.0 °C
30.0 °C
35%
75%
5%
0%
20%
100%
0.0 °C
0.0 °C
0.0 °C
2.5 °C
22.0 °C
5.0 °C
30.0 °C
7.0 °C
10.0 °C
2.0°C
30 °C
5.0 °C
39.0 °C
2.0 °C
9.0 °C
1.0 °C
5.0 °C
No
BEDIENUNGSANLEITUNG
DIE - auch teilweise - Vervielfältigung dieses Handbuchs ist strengstens untersagt.
DAS SETUP-MENÜ
Ausgehend vom Hauptdisplay werden durch Drücken der
Tasten AUFWÄRTS/ABWÄRTS folgende Seiten nacheinander
angezeigt:
Aktivierung Economy-Funktion
Aktivierung Verwendung elektrischer Heizwiderstand
Aktivierung Kontrolle der Mindesttemperatur
Aktivierung Feuchtigkeitskontrolle
Sollwert Feuchtigkeit
Sollte es nicht möglich sein, die Änderung einer oder mehrerer
Einträge aufzurufen, so sind zuvor die entsprechenden
Konfigurationsparameter einzugeben. Um zum Beispiel die
Verwendung des elektrischen Heizwiderstandes freizugeben,
ist zuvor im Menü zur Parameterkonfigurationen einzustellen,
dass dieser vorhanden sind.
EVO
FC66003554
Rev 00