It is now possible to connect all of the I/O boards to the
network.
Once the board has been set as SLAVE, it can
no longer communicate with any random user
unit. Accordingly, if the settings are changed, it
will be necessary to RESET it in the following
manner: disconnect the board from the
network and, keeping it powered, place digital
input 10 in short circuit for 15 seconds (clamps
I10 and IC).
All of the hydronic units (i.e. both MASTER
and SLAVE) connected to the network must be
configured in the same way.
MIXED NETWORK
The SMALL network on CONVEYED WAVES can also be
connected to a supervision network (ERGO or SMALL
solution) on RS485 through RS485 serial port of the
MASTER controller, thus obtaining what is known as a MIXED
NETWORK. Figure 04 illustrates the diagram of a mixed
network comprised of a SMALL network on CONVEYED
WAVES combined with a supervision network.
PARAMETER OUTLINING TABLE
ERGO
BMS
RS485
Slave from
MST/SLV
SPV
Protocol
Modbus
EVO Master: 0
Serial Address
1... 255
Based on the
Speed
Master
OC
MST/SLV
-
Serial Address
-
EN
19
SMALL
SMALL
RS485
OC
EVO Master:
EVO Master:
Master
-
EVO Slave:
EVO Slave:
Slave from
Slave from
SPV
Modbus
-
EVO Master: 0
-
EVO Slave:
EVO Slave:
1... 255
9600
-
EVO Master: Master
-
EVO Slave: Slave
EVO Master: 0
-
EVO Slave: 2... 255
IT IS strictly forbidden to reproduce this manual, even partially
Controller for units
MEANINGS OF THE LEDS
STATUS
LED
NETWORK
LED
Looking at the I/O board from the front, the
STATUS LED is on the left, while the NETWORK
LED is on the right.

TECHNICAL DATA

Power supply
Operating
Temperature
Storage Temperature
IP protection rating
Type of board
Output relay
Inputs
Temperature Probes
Mixed
Humidity probe
Network
Max cable section for
clamps
Master
Pollution rating
Heat/fire resistance
Over-voltage category Category II
SPV
EMC conformity
Modbus
standards
1... 255
9600
OPERATION MANUAL
BLUE
GREEN
Unit OFF
Unit ON
Communication
OC Master
OK
230Vac 50/60Hz
Power 2.5 W
Range 0-50°C
Range -10-60°C
IP30 (user unit)
Type 1.C
Normal Open 5A @ 240V (Resistive)
Max room temperature: 105°C
Micro-interruption
NTC Temperature Probes
0-5V probes on
Dry contacts (digital inputs)
NTC probes 10K Ohm @25°C
Range -25-100°C
Resistive type of probe
Range 20-90%RH
1.5 mm
2
Degree II
Category D
EN 61000-6-1(2007)
EN 61000-6-3(2007) + A1(2011)
EVO
RED
Alarm in
progress
No
communication
FC66003554
Rev 00