HOLDING REGISTER
(READING/WRITING WHOLES/ANALOGUES)
DESCRIPTION
1
Summer temperature SET (cooling)
2
Summer temperature SET minimum limit
3
Summer temperature SET maximum limit
4
Winter temperature SET (heating)
5
Winter temperature SET minimum limit
6
Winter temperature SET maximum limit
Single temperature SET
7
(if SUM/WIN on water/air temp.)
8
Humidity SET
9
Minimum humidity SET limit
10
Maximum humidity SET limit
Step ventilation speeds:
0 = extra-low speed
1 = low speed
11
2 = medium speed
3 = maximum speed
4 = AUTO speed
12
Modulating ventilation speed
INPUT REGISTER
(READ-ONLY WHOLES/ANALOGUES)
DESCRIPTION
1
Room temperature
2
Room humidity
3
Water temperature
4
Hot water temperature (only with 4-pipe units)
Step ventilation status:
0 = no ventilation
1 = extra-low speed
5
2 = low speed
3 = medium speed
4 = maximum speed
6
Modulating ventilation % value
7
% value of analogue output 1
8
% value of analogue output 2
9
% value of analogue output 3
10
Temperature SET on
11
Summer temperature SET
12
Winter temperature SET
Single temperature SET
13
(if SUM/WIN on water/air temp.)
14
Humidity SET on
15
Type of valve (NOT INCLUDED/ON-OFF/MODULATING)
EN
17
Controller for units
OPERATION MANUAL
IT IS strictly forbidden to reproduce this manual, even partially
ERGO GALLETTI MANAGEMENT SOFTWARE
If you are using ERGO Galletti management software it is also
possible to connect a Chiller/Heat pump to the supervision
system. In this way, the management software analyses the
system's data and adapts operation to the real needs.
ERGO management software can assign 4 different degrees
of freedom to the LCD controller, based on the type of
remote control that has been assigned through the software.
LOCAL: all of the functions are accessible on the
controller: speed choice, temperature, cooling or
heating mode, ON/OFF. All of the operation parameters
are read by the system.
REMOTE CONTROL A - cooling or heating mode is set
from the ERGO software; all of the other functions are
accessible on the controller: speed choice, temperature,
ON/OFF. All of the operation parameters are read by the
system.
REMOTE CONTROL B - The user can choose the
based on the value set through ERGO. The operating
mode is set by the software.
REMOTE CONTROL C - No function can be set on the
control panel, it is fully managed by the software.
"SMALL" NETWORK SOLUTIONS
"SMALL" network solutions constitute a MASTER/SLAVE
network system where one of the EVO controllers performs
the function of MASTER while all of the other EVO controllers
on the network perform the SLAVE function.
It can be set up in two different ways, each with different
functions and type of connection:
SMALL network on RS485
SMALL network on CONVEYED WAVES
EVO
FC66003554
Rev 00