How To Check How Many Units Are Connected; Additional Refrigerant Charge - Daikin CMSQ200A7W1B Manual De Instalación

Ocultar thumbs Ver también para CMSQ200A7W1B:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 96

11.4. How to check how many units are connected

It is possible to find out how many indoor units are active and
connected by operating the push-button switch on the printed circuit
board (A1P) of the working outdoor unit.
Make sure that all the indoor units connected to the outdoor unit are
active.
Follow the 5-step procedure as explained below.
The LEDs on the A1P shows the operating status of the outdoor
unit and the number of indoor units that are active.
x
w
OFF
The number of units that are active can be read from the LED
display in the "Monitor Mode" procedure below.
Example: in the following procedure there are 3 units active:
NOTE
Wherever during this procedure, press the
button if something becomes unclear.
BS1 MODE
You will return to setting mode 1 (H1P=
1
Setting mode 1 (default system status)
Default status (normal)
Press the
BS1 MODE
button to switch from setting mode 1 to monitor
mode.
2
Monitor mode
Default status display
To check the number of indoor units, press the
3
Monitor mode
Selection status of how many
connected indoor units to
display.
Pressing the
button causes the LED display to show the
BS3 RETURN
data on the number of indoor units that are connected.
4
Monitor mode
Displaying the number of
connected indoor units
Calculate the number of connected indoor units by adding the values of
all (H2P~H7P) blinking (c) LEDs together.
In this example: 2+1=3 units
Press the
button to return to step 1, setting mode 1
BS1 MODE
x
(H1P=
"OFF").
Installation manual
16
c
ON
Blinking
x
"OFF").
H1P H2P H3P H4P H5P H6P H7P
x x w x x x x
H1P H2P H3P H4P H5P H6P H7P
c x x x x x x
BS2 SET
button 5 times
H1P H2P H3P H4P H5P H6P H7P
c x x x w x w
H1P H2P H3P H4P H5P H6P H7P
c x x x x c c
32
16
8
4
2

11.5. Additional refrigerant charge

Follow the procedures below.
When charging a system, charging over the
permissible quantity can cause liquid hammer.
Always use protective gloves and protect your eyes
when charging refrigerant.
When the refrigerant charging procedure is done or
when pausing, close the valve of the refrigerant tank
immediately. If the tank is left with the valve open, the
amount of refrigerant which is properly charged may
get off point. More refrigerant may be charged by any
remaining pressure after the unit has stopped.
Electric shock warning
Close the electric box lid before turning on the main
power.
Perform the settings on the circuit board (A1P) of the
outdoor unit and check the LED display after the
power is on via the service lid which is in the lid of the
electric box.
Operate switches with an insulated
stick (such as a ball-point pen) to
avoid touching the life parts.
Make
sure
inspection cover into the switch box cover after the job
is finished.
If the power of some units is turned off, the charging
procedure can not be finished properly.
Make sure to turn ON the power 6 hours before
starting the operation. This is necessary to warm the
crankcase by the electric heater.
If operation is performed within 12 minutes after the
indoor and outdoor units are turned on, the H2P-LED
will be lit and the compressor will not operate.
See "11.3. Stop valve operation procedure" on
NOTE
page 15 for details on how to handle stop valves.
The refrigerant charging port is connected to the
piping inside the unit.
The unit's internal piping is already factory
charged with refrigerant, so be careful when
connecting the charge hose.
After adding the refrigerant, do not forget to close
the lid of the refrigerant charging port.
1
The tightening torque for the lid is 11.5 to
13.9 N•m.
In order to ensure uniform refrigerant distribution,
it may take the compressor ±10 minutes to start
up after the unit has started operation. This is not
a malfunction.
Charge with the outdoor unit at standstill
1.
Calculate how much refrigerant to be added using the formula
explained in the chapter "How to calculate the additional
refrigerant to be charged" on page 8.
2.
Valve A and the stop valves must be left closed, charge the
required amount of refrigerant through the liquid side stop valve
service port.
When the required amount of refrigerant is fully charged.
Record the amount of refrigerant that was added on the
additional refrigerant charge label provided with the unit and
attach it on the back side of the front panel. Perform the test
procedure as described in "Test operation" on page 20.
If the total refrigerant cannot be charged while the outdoor
unit is at standstill, it is possible to charge the refrigerant by
operating the outdoor unit using the refrigerant charge
function (refer to "Setting mode 2" on page 19).
to
re-attach
the
CMSQ200+250A7W1B
Air conditioning system
4PW47543-1

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Cmsq250a7w1b

Tabla de contenido