Setting Addresses; Sensing Room Temperature With The Built-In Sensor In A Remote Controller; Electrical Characteristics - Mitsubishi Electric CITY MULTI PEFY-P-VMHS-E Serie Manual De Instalación

Ocultar thumbs Ver también para CITY MULTI PEFY-P-VMHS-E Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 32

9.6. Setting addresses

(Be sure to operate with the main power turned OFF.)
[Fig. 9.6.1] (P. 4)
<Indoor controller board>
There are two types of rotary switch setting available: setting addresses 1 to 9
and over 10, and setting branch numbers.
1 How to set addresses
Example: If Address is "3", remain SW12 (for over 10) at "0", and match
SW11 (for 1 to 9) with "3".
2 How to set branch numbers SW14 (Series R2 only)
Match the indoor unit's refrigerant pipe with the BC controller's end con-
nection number. Remain other than R2 at "0".
The rotary switches are all set to "0" when shipped from the factory. These
switches can be used to set unit addresses and branch numbers at will.
The determination of indoor unit addresses varies with the system at site. Set
them referring to technical data.

9.8. Electrical characteristics

PEFY-P-VMHS-E
PEFY-P200VMHS-E
PEFY-P250VMHS-E
Refer to Data Book for other models.
Power supply
Volts / Hz
Range +-10%
220-240V / 50Hz
Max.: 264V
220-240V / 60Hz
Min.: 198V
Notes:
Please set the switch SW5 according to the power supply voltage.
Set SW5 to 240 V side when the power supply is 230 and 240 volts.
When the power supply is 220 volts, set SW5 to 220 V side.
9.7. Sensing room temperature with the
built-in sensor in a remote controller
If you want to sense room temperature with the built-in sensor in a remote control-
ler, set SW1-1 on the control board to "ON". The setting of SW1-7 and SW1-8 as
necessary also makes it possible to adjust the air flow at a time when the heating
thermometer is OFF.
Note:
To perform the auto cooling/heating operation, use the built-in sensor in a
remote controller or the optional remote sensor.
Symbols : MCA : Max. Circuit Amps ( = 1.25
IFM : Indoor Fan Motor
Output(kW)
MCA(A) (50 / 60Hz)
7.00
7.50
FLA) FLA : Full Load Amps
x
Output : Fan motor rated output
IFM
FLA(A) (50 / 60Hz)
0.87
5.60
0.87
6.00
13

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

City multi pefy-p200vmhs-eCity multi pefy-p250vmhs-e

Tabla de contenido