Electric Connection; Parameter Selection Sequence; Normal Operating Mode - VALPES ER Serie Documentación Tecnica Puesta En Servicio

Actuador eléctrico
Tabla de contenido

Publicidad

Electric connection

PARAMETER SELECTION SEQUENCE

1 Shunts positioning K1, K2 and K3
- Position the shunts as follows (before modification, switch off the card) :
ON
OFF
K3 OFF
K3 ON
2 Selection of the flow direction of the valve
2.1 Normal flow direction (by default)
- Press the OPEN button and apply the operating voltage to the card while keeping this button depressed.
G
- The green LED lights up. Release the OPEN button.
- Disconnect the card.
2.2 Inverse flow direction
- Press the CLOSE button and apply the operating voltage to the card while keeping this button depressed.
R
- The red LED lights up. Release the CLOSE button.
- Disconnect the card.
3 Selection of the type of set value
3.1 Voltage set value 0-10V
- Press the MEM button and apply the operating voltage to the card while keeping this button depressed.
R
- The red LED will light up 3 times. Release this button.
- Disconnect the card.
3.2 Current set value 0-20mA
- Press the MEM and OPEN buttons and apply the operating voltage to the card while keeping these but-
tons depressed.
R
- The red LED will light up 3 times. Release these buttons.
- Disconnect the card.
3.3 Current set value 4-20mA (by default)
- Press the MEM and CLOSE buttons and apply the operating voltage to the card while keeping these but-
tons depressed.
R
- The red LED will light up 3 times. Release these buttons.
- Disconnect the card.
4 Learning mode
- Press the OPEN and CLOSE buttons and apply the operating voltage to the card while keeping these but-
G
R
tons depressed.
- The 2 LEDs will light up. Release these buttons and the 2 LEDs will extinguish. The card is now in the
learning mode.
R
- Press the CLOSE button to put the valve in its closed position. The red LED will light up.
- Store this selected closed position by pushing MEM + CLOSE, the red LED will light up 3 times as a
R
confirmation of acknowledgement.
- Press the OPEN button to put the valve in its open position. The green LED will light up.
G
- Store this selected open position by pushing MEM + OPEN, the green LED will light up 3 times as a
confirmation of acknowledgement.
G
- Now, the positions selected have been stored. Disconnect the card.

NORMAL OPERATING MODE

- Apply the operating voltage to the card. The green LED will light up 3 times.
- Under normal operating conditions, the green LED will light up when the drive motor opens the valve, and
G
the red LED will light up when the drive motor closes it.
- If both LEDs remain extinguished, it means that the drive motor has not been triggered.
- In the case of an over torque, the motor stops and the 2 LEDS lights then together to indicate
G
R
the action of the torque limiter. To re-start it, you must either reverse the sense of rotation, either
switch the power off and on.
DSBA3200 rév.15/02/2010
Input signal
Output signal
0-10V
0-10V
0-10V
0-20mA
0-10V
4-20mA
0-20mA
0-10V
0-20mA
0-20mA
0-20mA
4-20mA
4-20mA
0-10v
4-20mA
0-20mA
4-20mA
4-20mA
Schunt K1
Schunt K2
A
B
A
B
ON
OFF
ON
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
GB
Schunt K3
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
14/24

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Er10Er20Er35Er60Er100

Tabla de contenido