Connecting The Storage System Temperature Sensor; Safety Instructions For Connecting The Storage System Temperature Sensor; Wiring Requirements For Connecting The Storage System Temperature Sensor; Storage System Temperature Sensor Connection Process - Ingeteam INGECON SUN STORAGE 1Play Serie Manual De Instalacion Y Uso

Ocultar thumbs Ver también para INGECON SUN STORAGE 1Play Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 105

Connecting the storage system temperature sensor

12. Connecting the storage system temperature sensor
Installing the storage system temperature sensor enables optimum charging to be carried out and extends battery
life.
This chapter explains the requirements and process for connecting the storage system temperature sensor to the
unit. Read carefully before starting the connection process.
Ingeteam recommends locating the sensor on a battery located in the central area of the storage
system. It should be placed approximately at the center, vertically, of the cell selected, and suitably
fixed in accordance with the installation specifications.
Use a 3-wire PT-100 temperature sensor.
12.1. Safety instructions for connecting the storage system
temperature sensor
Before you start to make the connections, make sure there is no voltage in the inverter. Check that
the AC protection of the auxiliary grid/genset and the DC switch are open.
Do not switch on the power to the unit until you have successfully made the rest of the connections
and the unit is closed.
12.2. Wiring requirements for connecting the storage system
temperature sensor
The wiring gauge for connecting the storage system temperature sensor is specified in the following table:
Temperature sensor wiring gauge
Cable diameter

12.3. Storage system temperature sensor connection process

To connect the temperature sensor:
1.
Loosen the corresponding packing gland (see Section "2.7. Description of wiring inlets"), remove the cap
and pass the sensor cable through it.
2.
Connect the wiring to terminal J60 PT-100, as indicated in the above figure, respecting the wiring colors.
The colors of the wires to connect to each terminal appear on the screen-printed electronic card (R: red, R: red,
W: white). Ingeteam recommends using a tubular terminal in accordance with DIN 46 228/1.
3.
Correctly tighten the packing glands to prevent losses to the protection class, verifying that the wiring is
not taut. Check that the connection is tight.
ABH2013IQM01_A - Installation and Operation Manual
INGECON SUN STORAGE 1Play
0.25 mm
2
~ 1.5 mm
2
4.5 ~ 10 mm
Ingeteam