8. Connection of the storage system
This chapter explains the requirements and process for connecting the storage system wiring to the unit. Read
carefully before starting the connection process.
8.1. Safety instructions for connecting the storage system
CAUTION
Before you start to make the connections, make sure there is no voltage in the inverter. Check that the
protections for the grid/genset, critical loads, storage system and PV array are open.
Do not switch on the power to the unit until you have successfully made the rest of the connections and the unit
is closed.
When carrying out the connections, respect the polarities marked on the electronic card. If the connection is
performed incorrectly the inverter could be damaged
Ingeteam accepts no liability for any damages caused by an incorrect connection.
8.2. Wiring requirements for connecting the storage system
The wiring specifications for connecting the storage system are specified in the following table:
Wiring gauge
Wiring diameter
Other specifications
26
INGECON SUN STORAGE 1Play TL M
Up to 32 A
Up to 40 A
4 mm
6 mm
2
9 ~ 13 mm
Ring terminal for M5 bolt
ABH2014IQM01_A- Installation and Operation Manual
Connection of the storage system
Up to 66 A
10 mm
2
2