YASKAWA CIPR-GA50C Serie Instrucciones De Instalación Y Operación página 24

200 v class, three-phase input: 0.1 to 22 kw / 200 v class, single-phase input: 0.1 to 4.0 kw / 400 v class, three-phase input: 0.37 to 30 kw
Ocultar thumbs Ver también para CIPR-GA50C Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 124
1 English
No.
Name
(Hex.)
A1-02
Control Method
Selection
A1-03
Initialize Parameters
b1-01
Frequency Reference
Selection 1
b1-02
Run Command
Selection 1
b1-03
Stopping Method
Selection
b1-04
Reverse Operation
Selection
C1-01
Acceleration Time 1
RUN
C1-02
Deceleration Time 1
RUN
C2-01
S-Curve Time @ Start
of Accel
C2-02
S-Curve Time @ End
of Accel
C2-03
S-Curve Time @ Start
of Decel
C2-04
S-Curve Time @ End
of Decel
C6-01
Normal / Heavy Duty
Selection
C6-02
Carrier Frequency
Selection
d1-01 - d1-16
Reference 1 to 16
RUN
d1-17
Jog Reference
RUN
d2-01
Frequency Reference
Upper Limit
24
Sets the control method for the drive application and the motor.
0: V/f Control, 2: Open Loop Vector, 5: PM Open Loop Vector,
6: PM Advanced Open Loop Vector, 8: EZ Vector Control
Sets parameters to default values.
0: No Initialization, 1110: User Initialization, 2220: 2-Wire Initialization,
3330: 3-Wire Initialization
Sets the input method for the frequency reference.
0: Keypad, 1: Analog Input, 2: Memobus/Modbus Communications,
3: Option PCB, 4: Pulse Train Input
Sets the input method for the Run command.
0: Keypad, 1: Digital Input, 2: Memobus/Modbus Communications,
3: Option PCB
Sets the method to stop the motor after removing a Run command or entering a
Stop command.
0: Ramp to Stop, 1: Coast to Stop, 2: DC Injection Braking to Stop,
3: Coast to Stop with Timer, 9: Stop with Constant Distance
Sets the reverse operation function. Disable reverse operation in fan or pump
applications where reverse rotation is dangerous.
0: Reverse Enabled, 1: Reverse Disabled
Sets the length of time to accelerate from zero to maximum output frequency.
Sets the length of time to decelerate from maximum output frequency to zero.
Sets the S-curve acceleration time at start.
Sets the S-curve acceleration time at completion.
Sets the S-curve deceleration time at start.
Sets the S-curve deceleration time at completion.
Sets the drive duty rating.
0: Heavy Duty Rating, 1: Normal Duty Rating
Sets the carrier frequency for the transistors in the drive.
1: 2.0 kHz, 2: 5.0 kHz (4.0 kHz AOLV/PM), 3: 8.0 kHz (6.0 kHz AOLV/PM),
4: 10.0 kHz (8.0 kHz AOLV/PM), 5: 12.5 kHz (10.0 kHz AOLV/PM),
6: 15.0 kHz (12.0 kHz AOLV/PM), 7: Swing PWM4 (Audible Sound 1),
8: Swing PWM4 (Audible Sound 2), 9: Swing PWM4 (Audible Sound 3),
A: Swing PWM4 (Audible Sound 4), B: Leakage Current Rejection PWM,
F: User Defined (C6-03 to C6-05)
Sets the frequency reference in the units from o1-03 [Frequency Display Unit
Selection.
Sets the Jog frequency reference in the units from o1-03 [Frequency Display
Unit Selection]. Set H1-xx = 6 [MFDI Function Select = Jog Reference
Selection] to use the Jog frequency reference.
Sets maximum limit for all frequency references. The maximum output
frequency is 100%.
YASKAWA TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction
WWW.NNC.IR
Description

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido