10 Attachment
The keypad shows oH3 and the drive continues operation. The output terminal set for Alarm
[H2-01 to H2-03 = 10] activates.
L1-04: Motor Thermistor oH Fault Select
No.
Name
(Hex.)
L1-04
Motor Thermistor
oH Fault Select
(0483)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. The output terminal set for Fault
[H2-01 to H2-03 = E] activates.
1 : Coast to Stop
The output turns off and the motor coasts to stop. The output terminal set for Fault [H2-01 to
H2-03 = E] activates.
2 : Fast Stop
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. The output
terminal set for Fault [H2-01 to H2-03 = E] activates.
◆
China RoHS Compliance
The China RoHS mark is displayed on products containing six specified hazardous substances
that are in excess of regulatory limits, based on the "Administrative Measures for the Restriction
of the Use of Hazardous Substances in Electrical and Electronic Products" and "Marking for the
Restricted Use of Hazardous Substances in Electronic and Electrical Products" (SJ/T 11364-
2014), which were promulgated on January 26, 2016. The number displayed in the center of the
mark indicates the environment-friendly use period (number of years) in which electrical and
electronic products that are being produced, sold, or imported to China can be used. The date of
manufacture of the electrical and electronic product is the starting date of the environment-
friendly use period for the product. The six specified hazardous substances contained in the
product will not leak outside of the product during normal use within this period and will have
no serious impact on the environment, the human body, or property.
The environment-friendly use period for this product is 15 years. This period is not the product
warranty period.
■
Information on Hazardous Substances in This Product
Table 10.3
shows the details on hazardous substances contained in this product.
278
Description
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the drive operation when the PTC input signal to the drive is
at the oH4 [Motor Overheat Fault (PTC Input)] detection level.
15
Figure 10.7 China RoHS Mark
YASKAWA TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction
WWW.NNC.IR
Default
(Range)
1
(0 - 2)