10 Attachment
■
Single-Phase 200 V Class
Table 10.9 Factory-Recommended Branch Circuit Protection: Single-Phase 200 V Class
Maximum Applicable Motor
Drive Model
B001
0.18 (1/6)
B002
0.37 (1/4)
B004
0.75 (3/4)
B006
1.1 (1.5)
B010
2.2 (3)
B012
3.0 (3)
B018
■
Three-Phase 400 V Class
Table 10.10 Factory-Recommended Branch Circuit Protection: Three-Phase 400 V Class
Maximum Applicable Motor
Drive Model
4001
0.37 (1/2)
4002
0.75 (1)
4004
1.5 (2)
4005
2.2 (3)
4007
3.0 (4)
4009
4.0 (5)
4012
5.5 (7.5)
4018
7.5 (10)
4023
11.0 (15)
4031
15.0 (20)
4038
18.5 (25)
282
Output
kW (HP)
ND
HD
0.1 (1/6)
0.25 (1/4)
0.55 (1/2)
1.1 (1)
1.5 (2)
2.2 (3)
-
4.0 (5)
Output
kW (HP)
ND
HD
0.37 (1/2)
0.55 (3/4)
1.1 (2)
1.5 (3)
2.2 (3)
3.0 (4)
4.0 (5)
5.5 (10)
7.5 (10)
11.0 (15)
15.0 (20)
YASKAWA TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction
WWW.NNC.IR
Semiconductor Protection Fuse
Time Delay
Fuse
Manufacturer: EATON/Bussmann
Class J, T, and
CC Fuse
Model
Rated Current
A
3
FWH-25A14F
6
FWH-25A14F
10
FWH-60B
15
FWH-80B
25
FWH-100B
30
FWH-125B
-
FWH-150B
Semiconductor Protection Fuse
Time Delay
Fuse
Manufacturer: EATON/Bussmann
Class J, CC,
and T Fuse
Model
Rated Current
A
3
FWH-40B
6
FWH-40B
10
FWH-50B
10
FWH-70B
15
FWH-70B
20
FWH-90B
25
FWH-90B
-
FWH-80B
-
FWH-100B
-
FWH-125B
-
FWH-175B
Rated Current
Input Rated
Current
A
25
25
60
80
100
125
150
Rated Current
Input Rated
Current
A
40
40
50
70
70
90
90
80
100
125
175