ECOFOREST TOKIO Manual De Instalación Y Mantenimiento página 30

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

The installation of the stoves must be done in the same way, for this reason, only the ECO III model will be
exposed. In the same way, air inlets and water connections will be missed in all drawings as section 4.11 indicates
the minimum security distances to be respected for their installation.
4.1.
Remove the packaging and the protective plastic.
4.2.
Remove the screws or bolts that fasten the stove to the pallet and remove it.
4.3.
If our model has a plastic protection, it must be removed before starting it.
4.4.
Mandatory stainless steel pipe (AISI 316L), never use aluminum, galvanized or iron pipe.
4.5.
In cases of humidity in the atmosphere above 60% is highly recommended installing a double-walled pipe of
stainless steel.
4.6.
If the stove is installed in a wooden house, the vertical pipe MUST be installed using double-wall insulation
and special attention should be paid to the area where it goes through the wall, isolated sockets are
mandatory.
4.7.
If the stove is mounted in a French style, a protective plate must be used to prevent a backflow of gases.
4.8.
Aluminium belt and silicone of high temperature (300
4.9.
Gas output must be located in a ventilated area, not in closed or half-closed areas e.g. garage, corridor, air
space of the house or places where gas may concentrate.
4.10. The external parts of the stove may reach high temperatures that might burn when touching; it is
recommended to use a non flammable grid to avoid risk of burn for children and old people.
The end of the gas outlet flex should remain higher than the stove's output. It is mandatory to install at least
two metres in length vertically to create natural current preventing smoke, odors or eventual cut of electric
supply.
The horizontal pipe must not be longer than 1 metre; greater lengths mean ash, condensation or corrosion
may build up in this area.
Faced with cut of electric supplies and unusual weather conditions (storms, strong winds) it is
recommendable to install an uninterruptible power supply (UPS) which we have available as an option. This
apparatus only feeds the exhaust vent.
4.11. Distances from doors, windows, ventilation grids or air input to the house or building:
A
Distance from ventilation grid.
B
Distance from ventilation grid.
C
Lateral side of a window.
D
Top of a window.
E
Top of a door.
F
Lateral side of a door.
G
Adjacent wall.
H
Height from adjacent wall.
I
Adjacent building.
4.12. The minimum distance from gas outlet to ground shall be minimum 65cm, depending however on the
surface. Gas may burn grass, plants, trees located near the gas outlet. In the event that the stove outlet is
lower, suitable safety measures should be taken. The outlet pipe should never be below the extractor itself.
4.13. The distance between gas outlet and public pavement shall be minimum 2.20 m. See your local regulations.
UNPACKING THE STOVE.
MATERIAL REQUIRED FOR INSALLATION.
SECURITY NORMS FOR GAS OUTPUT AND AIR INPUT.
500 mm
500 mm
1250 mm
650 mm
650 mm
1250 mm
300 mm
2300 mm
650 mm
C).
°
29
Drawing 4