Overall Dimensions; Electrical Connections - Ecoflam BLU 1700.1 P AB Manual De Instrucciones

Quemadores de gas de aire soplado
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

B LB 472 Blu 1700.1÷2000.1 P AB
MODELS
BLU 1700.1 PAB
BLU 2000.1 PAB
* Optional (only 1700.1)
All burners factory tested at 400 V 50 Hz three-phase for motors and 230 V 50 Hz monophase with neutral for auxi-
liary equipment. If mains supply is 230 V 50 Hz threephase withuot neutral, change position of connectors on burner
as in fig. Protect burner supply line with safety fuses and any other devices required by safety standards obtaining in the
country in question.
Once connected the burner to the gas pipeline, it is necessary to control that this last is perfectly sealed. Also verify that
the chimney is not obstructed. Open the gas cock and carefully bleed the piping through the pressure gauge connector,
then check the pressure value trough a suitable gauge. Power on the system and adjust the thermostats to the desired
temperature. When thermostats close, the sealing control device runs a seal test of valves; at the end of the test the bur-
ner will be enabled to run the start-up sequence.
PRELIMINARY CHECKS
Before starting up the boiler check the following:
• Gas type and feed pressure. • Gas valves closed.• The seals in the pipe fittings. • Gas pipe breather and input pressure.
• That the cable complies with the diagram and the phase and neutral wires correspond. • That the burner shuts down
when the boiler thermostat opens. • The seal of the boiler furnace which prevents air from entering. • The seal on the
flue-boiler pipe fitting. • The condition of the flue (sealed, free from blockage, etc.). If all these conditions are present,
start the burner. The control device starts the motor to carry out prewashing of the combustion chamber. During this
prewash period (about 30 seconds) the device checks that air pressure is correct via the air pressure switch. At the end, it
supplies power to the transformer and opens the gas valves. The flame must be lit and stabilize within 3 seconds, which
is the device's safety time limit. Check to ensure the flame is lit before placing any control instrument in the flue.
Adjust and check the gas flow necessary for the boiler at the meter. Adjust the air flow according to the gas flow to
obtain correct combustion.
IMPORTANT ADVICE
All adjustable parts must be fixed by the installer after making adjustments. Check flue combustion after each adjust-
ment. The CO
values must be approx. 9.7 (G20) 9.6 (G25 11.7 (l3B) 11.7 (l3P) and the CO must be less than 75
2
ppm.
IMPORTANT: to obtain the right adjustment of the combustion and thermal capacity it is important to analyze the
reducts of combustion with the aid of suitable instruments. The combustion and thermal capacity adjustment is done
simultaneously, together with the analysis of the products of combustion, making sure that the measured values are sui-
table and that they comply with current safety standards. On this matter, please refer to the table and figure below.
THESE OPERATIONS MUST BE DONE BY PROFESSIONALLY-QUALIFIED TECHNICIANS.

OVERALL DIMENSIONS

E
D - D1
N
A
B
C
D
710
385
325
340
730
405
325
346
D = Short head D1 = Long head

ELECTRICAL CONNECTIONS

CONNECTION TO THE GAS PIPELINE
START UP OF THE BURNER
ADJUSTING THE COMBUSTION PROCESS
A
B
D1
E
F
G
540
680
250
398 283*
546
680
270
398
pag.10
C
I
M
H
I
L
M
240
240
M14
283
240
240
M14
N
O
125
250
125
250

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Blu 2000.1 p ab

Tabla de contenido