Procedure for checking maximum concentration
Check the maximum concentration level in accordance with steps 1 to
2 below and take whatever action necessary to comply.
1 Calculate the amount of refrigerant (lbs. (kg)) charged to each
system separately.
Amount of refrigerant
Additional charging
in a single unit system
amount (amount of re-
+
(amount of refrigerant
frigerant added locally
with which the system
in accordance with the
is charged before leav-
length or diameter of
ing the factory)
the refrigerant piping)
NOTE
Where a single refrigerant facility is divided into 2 entirely independent
refrigerant systems then use the amount of refrigerant with which
each separate system is charged.
2 Follow local code requirements (ASHRAE-15 2007 & ASHRAE-34
2007).

19 . Disposal requirements

Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with relevant local and national
legislation.
45
Total amount
=
of refrigerant
(lbs. (kg)) in
the system